Shipping And Storage Conditions; Mechanical And Climatic Ambient Conditions For Operation - Siemens SIMATIC Compact FF Link Operating Instructions Manual

Bus link
Table of Contents

Advertisement

12.1.4

Shipping and storage conditions

Transport and Storage of Modules
The components described surpass the requirements for transport and storage conditions
according to the following standard:
IEC 61131 Teil 2.
The following information applies to modules transported or stored in their original packaging.
Type of condition
Free fall (in transport packaging)
Temperature
Atmospheric pressure
Relative humidity
Sinusoidal vibrations in accordance with the stand‐
ard:
IEC 60068‑2‑6
Shock according to IEC 60068-2-29
12.1.5

Mechanical and climatic ambient conditions for operation

Conditions of use
The described components are designed for use in a fixed, sheltered location. The operating
conditions exceed the requirements of the following standard:
IEC 61131 Part 2.
The described components meet the operating conditions according to standard:
ISA S71.4 G3
Use with additional measures
The described components must not be operated without additional measures:
● at locations with a high degree of ionizing radiation
● in aggressive environments caused, for example, by
– the development of dust
– corrosive vapors or gases
– strong electric or magnetic fields
● in installations requiring special monitoring, for example
– elevators
– electrical plants in potentially hazardous areas
An additional measure can be installation in a cabinet or in an enclosure, for instance.
Compact FF Link
Operating Instructions, 03/2015, A5E35651552-AA
12.1 General technical data
Permitted range
≤ 0.3 m
from -40 °C to + 85 °C
from 1080 to 660 hPa
(corresponds to an altitude of -1000 to 3500 m)
of 10 to 95 %, without condensation
5 to 8.4 Hz: 3.5 mm
8.4 to 500 Hz: 9.8 m/s
2
250 m/s
, 6 ms, 1000 shocks
2
Technical data
83