5.7 Input / Output Modules
Note
To ensure proper energy registration, this value must not be lower than the value calculated in
step 4.
5.7.3
Basic Settings
This dialog allows you to specify the I/O module (optionally) of your SICAM P.
There are two possibilities:
SICAM P is connected with PC (online)
1. Click the button Load slot configuration from device. The information will be loaded from
the device and displayed on the screen.
2. Parameterize the I/O modules.
3. Send the new configuration to the device.
Note
This procedure ensures that the I/O modules displayed on the screen correspond to those in the
device.
A parameter set is prepared for a later transmission to a SICAM P (offline).
1. Define slot A for the corresponding I/O module.
Note
These settings must correspond to the I/O modules in the device (refer to the ordering number,
see chapter 1.3)!