5.10 Updating the Firmware
5.10
Updating the Firmware
Proceed as follows to update the firmware:
1. Establish a connection to the device. From the menu bar, select Connection → Setup con-
nection and set the following parameters in the Setup device connection dialog:
•
Device connection: Serial connection
•
Device address: address 0 is valid for all devices
•
Interface: e.g. COM1
•
Baud rate: 9600 Baud at delivery
•
depends on adapter type RS485
Note
Make sure to set the same parameter values in SICAM P Parameterization and in the device. In
the device, the serial interface must be set to "PC-RS 485".
118
Power Meter SICAM P 7KG7750/55, Manual