5.7 Input / Output Modules
5.7.1
Binary / Relay Outputs
The SICAM P has two binary outputs. The devices are optionally equipped with a module with 3
additional relay outputs or a module with two binary outputs each.
In order to define the function of the two binary/relay outputs, select the binary output to be
parameterized in field Binary outputs → No. In the Contents field, you can assign this binary
output a function. You can select from the following options:
•
Off: binary output with no function
•
Device active: The SICAM P active function allows you to monitor whether the device is
switched on (contact closed). If there is no contact, the device is switched off or broken.
•
Limit values: Here, you can output the limit value group signals via the binary outputs. The
pulse length indicates how long the binary contact is closed by means of a signal from a limit
value group.
•
Energy counter: If you assign this function to a binary output, the consumption or supply of
the selected work is output as a pulse. Select a measured value and the related measure-
ment point. Set a limit value (energy increase per pulse) for which a pulse should be trig-
gered. The parameterizable range (minimum and maximum value) can be found by entering
the max. consumer power in the field Help. The pulse duration can be selected in increments
of 50 ms between 50 ms and 500 ms in the Pulse field .
You will find a description of the energy pulse measurement in chapter 5.7.2.
•
Direction of rotation: output the rotation direction of the voltage
•
1: Contact activated: Direction of rotation for clockwise display (phase sequence A-B-C,
clockwise rotation)
•
0: Contact deactivated: Direction of rotation for anti-clockwise display (2 phases inter-
changed, anti-clockwise rotation)
92
Power Meter SICAM P 7KG7750/55, Manual
E50417-B1076-C340-A6, Edition 09.2013