6

6.1 Overview

6.1
Overview
SICAM P can be adjusted either directly from the device using the buttons on the front panel or
by using the SICAM P programming software.
You can select the measurement range under Basic Settings → Connection / Transformer.
Only the measurement ranges selected for current and voltage inputs can be adjusted in the Cal-
ibration menu.
Adjusting the SICAM P requires a single-phase adjusting device that can generate voltages and
currents, e.g. Omicron CMC 256+EP. Adjustment frequency: 50 Hz or 60 Hz.
Note
To be able to make adjustments using the software, a connection must be established between
the PC and the SICAM P device.
Before starting the adjustment, you should set the time in the SICAM P. This ensures that the
last adjustment is displayed with a date in the SICAM P.
When connecting the adjusting outputs to the appropriate inputs, make sure that the SICAM P
is correctly connected as per the Connection Diagrams for adjustment.
The following three elements should be adjusted during the adjustment process:
Voltage inputs V
Current inputs I
128
Power Meter SICAM P 7KG7750/55, Manual
E50417-B1076-C340-A6, Edition 09.2013