Device Code - Siemens SICAM P 7KG7750 Manual

Power meter
Hide thumbs Also See for SICAM P 7KG7750:
Table of Contents

Advertisement

5
5.8 Additionals
Power direction
This parameter allows you to set the operating mode of the SICAM P:
Load (industry mode, standard)
this means:Power positive = Energy demand
Generator (Power generation mode)
this means:Power negative = Energy demand
Counter assignment
Internal counters 1 to 4 can be displayed in the digital measured value screens of the SICAM P.
You can assign the four internal counters to the max. 6 limit values groups here.
Zero point suppression
The zero suppression enables the definition of the measuring range start in % of the measuring
range end. Can be selected from 0.0 % to 10.0 % of the upper limit of the measurement range
(default setting: 1.000 %).
Note
Due to its high precision, SICAM P can measure voltages and currents even without measuring
values connected to the device. If you do not want this behaviour in your application, you can
suppress measuring below a certain threshold.
5.8.2

Device Code

Setting the device code secures the SICAM P against unauthorized changes.
When the code is activated, you are prompted to enter the password when you call up the
102
Power negative = Energy supply
Power positive = Energy supply
Power Meter SICAM P 7KG7750/55, Manual
E50417-B1076-C340-A6, Edition 09.2013