Analog Outputs (Optional) - Siemens SICAM P 7KG7750 Manual

Power meter
Hide thumbs Also See for SICAM P 7KG7750:
Table of Contents

Advertisement

2. Parameterize the I/O modules.
3. Send the new configuration to the device, as soon as the connection to the device has been
established.
5.7.4

Analog Outputs (optional)

The analog outputs (optional) allow you to output internal measurement values as analog values
in the range of 0 mA to 20 mA. This feature represents a measuring transducer.
Proceed as follows:
1. Please select Slot A to configure analog outputs.
2. Activate/Deactivate one or both analog outputs by ticking the corresponding check box under
1. and/or 2.
3. For each analog output used, choose the Measured value together with the Test point and
set the signal range in the fields from and to.
4. Select the current range of the I/O module: 0..20 mA or 4..20 mA.
Note
The output of analog values can be controlled via Modbus, IEC 60870-5-103 or Profibus proto-
col. Select the output mode first in screen further setting (see chapter 4.4.8) in AO settings
and choose holding or default mode in screen Analog output settings.
Deactivate the channel which will be controlled by communication protocol in dialog Analog out-
puts.