6.2

Connection Diagrams for Adjustment

Correct adjustment is crucial to the accuracy of the measurements made by the SICAM P.
The following applies to the adjustment of current and voltage inputs of the SICAM P:
Single-phase current and voltage connection.
Frequency 50 Hz or 60 Hz.
There must be no phase shift between current and voltage.
Connect the device terminals „Ground" (terminal block H) and „N" (terminal block F) with ter-
minal "N" on the adjusting device.
The SICAM P must be grounded.
Power Meter SICAM P 7KG7750/55, Manual
E50417-B1076-C340-A6, Edition 09.2013