1
1.6 Interface and Terminals
1.6.5
Mounting
WARNING
Warning about dangerous voltages when operating an electrical device.
Nonobservance of the safety instructions means that death, severe
injuries or considerable material damages can occur.
•
The SICAM P is a build-in device and must therefore be in-stalled on a switchboard or in a
control cabinet. After installation, it is important that all terminals are properly covered to pre-
vent accidental contact with energized parts.
To mount the device proceed as follows:
•
Swing the mounting element (provided with the device) over the rear cone.
•
Move the mounting element to the position. Use a screw driver (0.6 x 4.5) mm to fix the moun-
ting elements until the slipping clutch takes effect.
Fig. 1-9
Mounting
Notes
•
The device location should be largely free from vibrations.
•
The device must be operated within allowable ambient temperature limits. Operating the
device outside of the operating temperature range can lead to measurement errors and
device failure.
•
Steps should be taken to minimize exposure of the device to direct sun light and large tem-
perature variations.
•
Minimum thickness of the mounting plate: 1 mm; steel.
•
Steps must be taken to prevent condensation on or within the device during operation.
•
To prevent accidental contact with energized parts the above described mounting must be
taken care-fully and correctly.
30
Power Meter SICAM P 7KG7750/55, Manual
E50417-B1076-C340-A6, Edition 09.2013