Carrier Omnizone 50BVC Installation, Start-Up, Service And Controls Operation And Troubleshooting page 88

Water-cooled indoor self-contained systems
Table of Contents

Advertisement

PROTOCOL MAP
READ/
DISPLAY NAME
WRITE
Static Press Set
Holding Regis-
R/W
point
Static Pressure
Holding Regis-
R/W
Shutdown
Supply Air Tem-
R
perature
Supply Air Set Point
Holding Regis-
R/W
Trip
Supply Air Set Point
Holding Regis-
R/W
Differential
Supply Air Temp
R
Set Point
System Status
R
Holding Regis-
Unit_mode
R/W
UPM INPUT
R
UPM INPUT
R
UPM Reset
R/W
UPM Reset
R/W
ZN_CO2_fail
R
ZN_CO2_HI
R
Holding Regis-
Zone Co2 High Trip
R/W
LEGEND
BAS
— Building Automation System
DAT
— Discharge Air Temperature
LWT
— Leaving Water Temperature
R
— Read
UPM
— Unit Protection Module
W
— Write
Table 66 — Integration Points List (cont)
MODBUS
REGISTER
REGISTER
REFERENCE
TYPE
NUMBER
NAME
41
ter (Float)
press_stpt
43
st_press_trip
ter (Float)
Input Register
39
eff_sat
(Float)
45
sat_hi_trip
ter (Float)
47
sat_stpt_diff
ter (Float)
Input Register
41
sa_setpt
(Float)
Input Register
43
sys_status
(Float)
49
unit_mode
ter (Float)
Discrete Input
67
upm_input
Discrete Input
68
upm2_input
Coil
11
upm_rst
Coil
12
upm2_rst
Discrete Input
69
zn_co2_fail
Discrete Input
70
zn_co2_hi
51
ter (Float)
co2_hi_trip
BACNET
OBJECT
OBJECT
TYPE
ID
sta_-
AV
52
AV
69
AV
10
AV
63
AV
65
AV
31
AV
16
AV
23
BV
39
BV
59
BV
25
BV
60
BV
51
BV
48
zn_-
AV
27
88
LONWORKS
NV NAME
SNVT
Network Parameter to
nviSta-
SNVT_-
set the Duct Static Pres-
PressStpt
press_p(113)
sure Set point in inches
of H2O Setup
Network Parameter to
set Static Pressure Shut-
down trip
Select
0 = Single Pressure
Value
1 = Multiple Pressure
Values (Default)
Network Parameter to set
Supply Air Temperature
nvoEffSA-
SNVT_-
0 = Hardwired Sensor
Temp
temp_p(105)
(Default)
1 = BAS Sensor Value
Network Parameter to set
Supply Air Set point trip
Select
0 = Single Set point Value
1 = Multiple Set point
Values (Default)
Network Parameter set
Supply Air Set point dif-
ferential
Select
0 = Single Set point
Value
1 = Multiple Set point
Values (Default)
Network Parameter to
set Supply Air Tempera-
SNVT_-
ture Set point
nviSAtStpt
temp_p(105)
0 = Hardwired Sensor
(Default)
1 = BAS Sensor Value
General System Status
0 = Unoccupied
1 = Occupied
nvoSys-
SNVT_count_inc(
2 = Fan Only
Status
9)
4 = Cooling
5 = Transition to Cool
10 = Re-Heat
Network Parameter to
configure Unit operating
mode
Select
0 = Cooling only
5 = Cooling + Hot Gas
Re-Heat
UPM Input Failure Alarm
- Board 1
Select
0 = UPM Connected
1 = UPM Connection
Failure
UPM Input Failure Alarm
- Board 1
Select
0 = UPM Connected
1 = UPM Connection
Failure
UPM Board 1 Reset.
Select
Momentary On/Off
required.
UPM Board 2 Reset.
Select
Momentary On/Off
required.
CO
(Sensor)
Select
0 = Normal
1 = Sensor Failure
(Check Sensor Hardware)
CO
(High)
Select
0 = Normal
1 = High CO
(Default: >1995 PPM)
Network Alarm indicat-
Select
ing status of high levels
of CO
OPERATION
DESCRIPTION
2
Zone Sensor Alarm
2
Zone Sensor Alarm
2
Level
2

Advertisement

Table of Contents
loading

Table of Contents