Carrier Omnizone 50BVC Installation, Start-Up, Service And Controls Operation And Troubleshooting page 45

Water-cooled indoor self-contained systems
Table of Contents

Advertisement

GROUP NUMBER
99
10
11
12
13
14
15
16
20
21
22
26
*Refer to Motor name plate.
Table 22 — VFD Factory Default Settings
ABB 550 DRIVE FACTORY CONFIGURATION VFD 1
PARAMETER NUMBER
9902
9904
9905
9906
9907
9908
9909
1001
1002
1003
1103
1104
1105
1201
1202
1301
1302
1303
1304
1305
1306
1401
1402
1403
1507
1508
1509
1510
1511
1512
1601
1608
1609
2002
2003
2007
2008
2101
2102
2202
2203
2605
2606
2607
DESCRIPTION
Application Macro
Motor control Mode
Motor Nominal Voltage
Motor Nominal Current
Motor Nominal Frequency
Motor Nominal Speed
Motor Nominal Power
EXT1 Commands
EXT2 Commands
Direction
REF1 Select
REF1 Minimum
REF 1 Maximum
Constant Speed Select
Constant Speed Value (Field
Programmable)
Minimum AI-1
Maximum AI-1
Filter AI-1
Minimum AI-2
Maximum AI-2
Filter AI-2
Relay Output 1
Relay Output 2
Relay Output 3
AO2 Content
AO2 Content Min
AO2 Content Max
Minimum AO2
Maximum AO2
Filter AO2
Run Enable
Start Enable 1
Start Enable 2
Minimum Fan Speed
Maximum Current
Minimum Frequency
Maximum Frequency
Start Function
Stop Function
Accelerate Time
Decelerate Time
Volt/ Freq Ratio
Switching Frequency
Switching Frequency Control
45
VALUE
HVAC Default
Scalar
DI1 - Start/Stop
N/A
Forward
AI-1
0Hz at 60Hz/ 0Hz at 50Hz
60 Hz at 60Hz / 50 Hz at 50Hz
NOT SEL
6Hz - Motor Nominal Frequency
0%
100%
1 Sec
0%
100%
1 Sec
Ready
Run
Fault (Inverted)
AI-1 (Used to control VFD2 Reference)
0%
100%
0.0mA
20.0mA
1 Sec
DI-1
DI-4
N/A
0
30% higher that Motor (s) FLA
0Hz
60Hz / 50Hz (Per motor frequency rating)
Fly Start
Coast
30 Seconds
30 Seconds
Square
4Khz
ON