Table 12 — Electrical Data — with Belt Drive Motor, Inverter Duty (50BVJ)
RATED
MODELS
VOLTAGE
208-230/3/60
208-230/3/60
208-230/3/60
460/3/60
20
460/3/60
460/3/60
575/3/60
575/3/60
575/3/60
208-230/3/60
208-230/3/60
208-230/3/60
24
460/3/60
460/3/60
460/3/60
575/3/60
575/3/60
575/3/60
208-230/3/60
208-230/3/60
28
460/3/60
460/3/60
575/3/60
575/3/60
34
208-230/3/60
460/3/60
LEGEND
FLA
— Full Load Amps
HP
— Horsepower
LRA
— Locked Rotor Amps
RLA
— Rated Load Amps
COMPRESSOR
VOLTAGE
RLA
MIN/MAX
QTY
(EACH)
197/253
2
29.5
197/253
2
29.5
197/253
2
29.5
414/506
2
14.7
414/506
2
14.7
414/506
2
14.7
518/632
2
12.2
518/632
2
12.2
518/632
2
12.2
197/253
2
30.1
197/253
2
30.1
197/253
2
30.1
414/506
2
16.7
414/506
2
16.7
414/506
2
16.7
518/632
2
12.2
518/632
2
12.2
518/632
2
12.2
197/253
2
48.1
197/253
2
48.1
414/506
2
18.6
414/506
2
18.6
518/632
2
14.7
518/632
2
14.7
197/253
2
55.8
414/506
2
26.9
INDOOR FAN MOTOR
LRA
MOTOR
MOTOR
(EACH)
HP
QTY
195.0
2.0
2
195.0
3.0
2
195.0
5.0
2
95.0
2.0
2
95.0
3.0
2
95.0
5.0
2
80.0
2.0
2
80.0
3.0
2
80.0
5.0
2
225.0
2.0
2
225.0
3.0
2
225.0
5.0
2
114.0
2.0
2
114.0
3.0
2
114.0
5.0
2
80.0
2.0
2
80.0
3.0
2
80.0
5.0
2
245.0
3.0
2
245.0
5.0
2
125.0
3.0
2
125.0
5.0
2
100.0
3.0
2
100.0
5.0
2
340.0
5.0
2
173.0
5.0
2
29
POWER SUPPLY
MIN
FLA
MAX FUSE/
CIRCUIT
(EACH)
HACR
AMPS
6.2
78.8
100
8.8
84.0
110
13.5
93.4
110
3.1
39.3
50
4.3
41.7
50
6.2
45.5
60
2.0
31.5
40
3.5
34.4
45
4.5
36.5
45
6.2
80.1
110
8.8
85.3
110
13.5
94.7
110
3.1
43.8
60
4.3
46.2
60
6.2
50.0
60
2.0
31.5
40
3.5
34.4
45
4.5
36.5
45
8.8
125.8
150
13.5
135.2
175
4.3
50.5
60
6.2
54.3
70
3.5
40.0
50
4.5
42.1
50
13.5
152.6
200
6.2
72.9
90