Carrier Omnizone 50BVC Installation, Start-Up, Service And Controls Operation And Troubleshooting page 81

Water-cooled indoor self-contained systems
Table of Contents

Advertisement

PROTOCOL MAP
READ/
DISPLAY NAME
WRITE
C1_HAND
R
Discrete Input
C2_FAIL
R
Discrete Input
C2_HAND
R
Discrete Input
C3_FAIL
R
Discrete Input
C3_HAND
R
Discrete Input
C4_FAIL
R
Discrete Input
C4_HAND
R
Discrete Input
CMP1_RNTM
R
Discrete Input
CMP2_RNTM
R
Discrete Input
CMP3_RNTM
R
Discrete Input
CMP4_RNTM
R
Discrete Input
Holding Regis-
CO2 Sensor Ena
R/W
Coil Configuration
Input Register
R
Status
Comp Stage1 Out-
R
Discrete Input
put Cmd
Comp Stage2 Out-
R
Discrete Input
put Cmd
Comp Stage3 Out-
R
Discrete Input
put Cmd
Comp Stage4 Out-
R
Discrete Input
put Cmd
Table 66 — Integration Points List (cont)
MODBUS
REGISTER
REGISTER
REFERENCE
TYPE
NUMBER
NAME
9
comp1_hand
10
comp2_fail
11
comp2_hand
12
comp3_fail
13
comp3_hand
14
comp4_fail
15
comp4_hand
16
comp1_rntm
17
comp2_rntm
18
comp3_rntm
19
comp4_rntm
co2_sen-
9
ter (Float)
sor_ena
coil_cfg_sta-
3
(Float)
cmp_stg1_cm
20
cmp_stg2_cm
21
cmp_stg3_cm
22
cmp_stg4_cm
23
BACNET
OBJECT
OBJECT
TYPE
ID
BV
151
BV
154
BV
155
BV
157
BV
158
BV
160
BV
161
BV
35
BV
36
BV
69
BV
71
AV
26
AV
150
tus
BV
11
d
BV
12
d
BV
66
d
BV
67
d
81
LONWORKS
NV NAME
SNVT
Network Alarm indicat-
ing compressor is run-
Select
ning but the controller is
not issuing an automatic
command.
Network Alarm indicat-
ing compressor com-
Select
manded to run but no
current feedback is
sensed
Network Alarm indicat-
ing compressor is run-
Select
ning but the controller is
not issuing an automatic
command.
Network Alarm indicat-
ing compressor com-
Select
manded to run but no
current feedback is
sensed
Network Alarm indicat-
ing compressor is run-
Select
ning but the controller is
not issuing an automatic
command.
Network Alarm indicat-
ing compressor com-
Select
manded to run but no
current feedback is
sensed
Network Alarm indicat-
ing compressor is run-
Select
ning but the controller is
not issuing an automatic
command.
Compressor 1 Runtime
Alarm Status, (8760
Select
Hours)
0 = Off
1 = Timer Has Expired
Compressor 2 Runtime
Alarm Status, (Hours)
Select
0 = Off
1 = Timer Has Expired
Compressor 3 Runtime
Alarm Status (Hours)
Select
0 = Off
1 = Timer Has Expired
Compressor 4 Runtime
Alarm Status (Hours)
Select
0 = Off
1 = Timer Has Expired
Zone CO
Enable Setup
0 = No CO
1 = CO
Select
2 = CO
3 = CO
4 = CO
5 = Open Damper as Fan
runs
Network Status of Coil
Configuration
Select
0 = Parallel
1 = Series
Compressor Stage 1
Output Status
nvoC-
SNVT_switch(95)
0 = Compressor Stage 1
mp1Cmd
Off
1 = Compressor 1 On
Compressor Stage 2
nvoC-
Output Status
SNVT_switch(95)
mp2Cmd
0 = Compressor 2 Off
1 = Compressor 2 On
Compressor Stage 3
nvoC-
Output Status
SNVT_switch(95)
mp3Cmd
0 = Compressor 3 Off
1 = Compressor 3 On
Compressor Stage 2
nvoC-
Output Status
SNVT_switch(95)
mp4Cmd
0 = Compressor 4 Off
1 = Compressor 4 On
OPERATION
DESCRIPTION
2
Sensor
2
(Default)
2
Monitoring
2
+ Damper
2
BAS Monitoring
2
BAS + Damper