Carrier Omnizone 50BVC Installation, Start-Up, Service And Controls Operation And Troubleshooting page 85

Water-cooled indoor self-contained systems
Table of Contents

Advertisement

PROTOCOL MAP
READ/
DISPLAY NAME
WRITE
HP2
R
Discrete Input
HP3
R
Discrete Input
HP4
R
Discrete Input
INPUT_LOCK
R
Discrete Input
Loop Enabled
R/W
LOW SP
R
Discrete Input
LP1
R
Discrete Input
LP2
R
Discrete Input
LP3
R
Discrete Input
LP4
R
Discrete Input
LVG_HI
R
Discrete Input
LVG_LO
R
Discrete Input
LVG_SENS_FAIL
R
Discrete Input
Input Register
Mode Status
R
Holding Regis-
OAT Reset
R/W
Holding Regis-
OAT Reset 2
R/W
Table 66 — Integration Points List (cont)
MODBUS
REGISTER
REGISTER
REFERENCE
TYPE
NUMBER
NAME
44
hp2_2st
45
hp3_3st
46
hp4_4st
47
input_lock
Coil
9
loop_enabled
sta_-
48
press_low
49
lp1_2st
50
lp2_2st
51
lp3_3st
52
lp4_4st
53
lvg_hi
54
lvg_lo
55
lvg_sen
33
mode_status
(Float)
21
oat_reset1
ter (Float)
23
oat_reset2
ter (Float)
BACNET
OBJECT
OBJECT
NV NAME
TYPE
ID
nvoHp2Ala
BV
52
rm
nvoHp3Ala
BV
7
rm
nvoHp4Ala
BV
54
rm
BV
38
nviLoopEn
BV
23
a
BV
81
nvoLp1Ala
BV
4
rm
nvoLp2Ala
BV
53
rm
nvoLp3Ala
BV
6
rm
nvoLp4Ala
BV
55
rm
BV
32
BV
33
BV
34
nvo-
AV
24
ModeSta-
tus
nviO-
AV
80
atReset1
nviO-
AV
72
atReset2
85
LONWORKS
OPERATION
SNVT
DESCRIPTION
UPM Board 2 High Pres-
sure Alarm Status for
Compressor 3
SNVT_switch(95)
0 = Normal
1 = Active High Pressure
3 Alarm
UPM Board 1 High Pres-
sure Alarm Status for
Compressor 2
SNVT_switch(95)
0 = Normal
1 = High Pressure 2
Alarm
UPM Board 2 High Pres-
sure Alarm Status for
Compressor 4
SNVT_switch(95)
0 = Normal
1 = High Pressure 4
Alarm
Network Parameter to
set INPUT LOCK
Select
0 = Hardwired Sensor
(Default)
1 = BAS Sensor Value
Network Parameter to
set Loop Enabled
SNVT_switch(95)
0 = Hardwired Sensor
(Default)
1 = BAS Sensor Value
Network Parameter to
set LOW SP
Select
0 = Single LOW Value
1 = Multiple LOW Values
(Default)
UPM Board 1 Low Pres-
sure Alarm Status for
SNVT_switch(95)
Compressor 1
0 = Normal
1 = LP1 Alarm Active
UPM Board 2 Low Pres-
sure Alarm Status for
SNVT_switch(95)
Compressor 3
0 = Normal
1 = LP3 Alarm Active
UPM Board 1 Low Pres-
sure Alarm Status for
SNVT_switch(95)
Compressor 2
0 = Normal
1 = LP2 Alarm Active
UPM Board 2 Low Pres-
sure Alarm Status for
SNVT_switch(95)
Compressor 4
0 = Normal
1 = LP4 Alarm Active
Leaving Water Tempera-
ture Alarm (High)
Select
0 = Normal
1 = High LWT Alarm
Active (Default: >135 °F)
Leaving Water Tempera-
ture (LWT) Alarm (Low)
Select
0 = Normal
1 = Low LWT Alarm
Active (Default: <33 °F)
Leaving Water Tempera-
ture Alarm (Sensor)
0 = Normal
Select
1 = Sensor Failure
(Check Sensor Hardware
Configuration)
Unit Mode of Operation
Selection Status
SNVT_count_inc(
0 = Cooling only
9)
5 = Cooling + Hot Gas
Re-Heat
Outside Air Temperature
SNVT_count_inc(
(Free Cooling) Opera-
9)
tion in °F
Default: 50 °F
Outside Air Temperature
SNVT_count_inc(
(Stage 1 Cooling) Opera-
9)
tion in °F
Default: 60 °F