Carrier Omnizone 50BVC Installation, Start-Up, Service And Controls Operation And Troubleshooting page 41

Water-cooled indoor self-contained systems
Table of Contents

Advertisement

5.
Connect the analog output wiring to the screw terminals on
the I/O Flex 6126 controller and to the controlled device
(Fig. 30).
Fig. 30 — Analog Output Diagram
6.
Set the AO Mode Select jumper to the type of device the out-
put is being wired to.
7.
Turn on the I/O Flex 6126 controller's power (Fig. 31).
I/O Flex EX8160 Expander Module
GENERAL DESCRIPTION
The I/O Flex EX8160 expander expands the input/output capabili-
ty of the I/O Flex 6126 controller. The I/O Flex 6126 controller
supports one I/O Flex EX8160 expander.
The I/O Flex EX8160 expander is mounted onto the I/O Flex 6126
controller enclosure.
The expander may also be mounted separately within the mount-
ing enclosure. Screw the I/O Flex EX8160 expander into an en-
closed panel using the mounting holes provided on the cover plate.
Be sure to leave about 2 inches (5 centimeters) on each side for
wiring. Connect the I/O Flex EX8160 expander to the I/O Flex
6126 controller before applying power to either one. See Fig. 32.
Connecting I/O Flex EX8160 Expander and I/O Flex 6126
Controller
1.
Turn off the power to both the I/O Flex EX8160 expander
and the I/O Flex 6126 controller.
2.
Wire the screw terminals connecting each devices' XNET
Remote Expansion connector.
3.
Turn on the power to both the I/O Flex EX8160 expander and
the I/O Flex 6126 controller.
VAV Control Parameters, Status, and Alarms
Control
Integral occupancy schedule
External occupancy control: Manual ON, BAS command,
or DI Enable
Supply Fan and VFD control
Compressor 1 control
Compressor 2 control
Compressor 3 control
Compressor 4 control
Unit Enable manual control (optional)
Modulating HGRH control
Condenser water valve control
Waterside Economizer control
Outdoor Air Damper (OAD) control (enable)
Return Fan control (enable)
Status
Cooling control status
Cooling demand percentage (0 to 100%)
Supply air temperature
Return air temperature
Leaving water temperature
Entering water temperature
Fan-Hours runtime counter (filter replacement indicator)
Fan starts counter
Compressor 1 starts counter
Compressor 2 starts counter
Compressor 3 starts counter
Compressor 4 starts counter
Alarms
Leaving water temperature high/low trip
Discharge air temperature high/low trip
Entering water temperature high/low trip
Sensor failure alarm
Unit filter runtime trip (optional)
Comp 1 runtime trip
Comp 2 runtime trip
Comp 3 runtime trip
Comp 4 runtime trip
Freeze stat sensor UPM alarm (optional)
Low pressure sensor UPM alarm
High pressure sensor UPM alarm
Low pressure sensor UPM alarm
High pressure sensor UPM alarm
Condensate overflow UPM alarm
High/low voltage UPM alarm
41