5.
Connect the analog output wiring to the screw terminals on
the I/O Flex 6126 controller and to the controlled device
(Fig. 30).
Fig. 30 — Analog Output Diagram
6.
Set the AO Mode Select jumper to the type of device the out-
put is being wired to.
7.
Turn on the I/O Flex 6126 controller's power (Fig. 31).
I/O Flex EX8160 Expander Module
GENERAL DESCRIPTION
The I/O Flex EX8160 expander expands the input/output capabili-
ty of the I/O Flex 6126 controller. The I/O Flex 6126 controller
supports one I/O Flex EX8160 expander.
The I/O Flex EX8160 expander is mounted onto the I/O Flex 6126
controller enclosure.
The expander may also be mounted separately within the mount-
ing enclosure. Screw the I/O Flex EX8160 expander into an en-
closed panel using the mounting holes provided on the cover plate.
Be sure to leave about 2 inches (5 centimeters) on each side for
wiring. Connect the I/O Flex EX8160 expander to the I/O Flex
6126 controller before applying power to either one. See Fig. 32.
Connecting I/O Flex EX8160 Expander and I/O Flex 6126
Controller
1.
Turn off the power to both the I/O Flex EX8160 expander
and the I/O Flex 6126 controller.
2.
Wire the screw terminals connecting each devices' XNET
Remote Expansion connector.
3.
Turn on the power to both the I/O Flex EX8160 expander and
the I/O Flex 6126 controller.
VAV Control Parameters, Status, and Alarms
Control
•
Integral occupancy schedule
•
External occupancy control: Manual ON, BAS command,
or DI Enable
•
Supply Fan and VFD control
•
Compressor 1 control
•
Compressor 2 control
•
Compressor 3 control
•
Compressor 4 control
•
Unit Enable manual control (optional)
•
Modulating HGRH control
•
Condenser water valve control
•
Waterside Economizer control
•
Outdoor Air Damper (OAD) control (enable)
•
Return Fan control (enable)
Status
•
Cooling control status
•
Cooling demand percentage (0 to 100%)
•
Supply air temperature
•
Return air temperature
•
Leaving water temperature
•
Entering water temperature
•
Fan-Hours runtime counter (filter replacement indicator)
•
Fan starts counter
•
Compressor 1 starts counter
•
Compressor 2 starts counter
•
Compressor 3 starts counter
•
Compressor 4 starts counter
Alarms
•
Leaving water temperature high/low trip
•
Discharge air temperature high/low trip
•
Entering water temperature high/low trip
•
Sensor failure alarm
•
Unit filter runtime trip (optional)
•
Comp 1 runtime trip
•
Comp 2 runtime trip
•
Comp 3 runtime trip
•
Comp 4 runtime trip
•
Freeze stat sensor UPM alarm (optional)
•
Low pressure sensor UPM alarm
•
High pressure sensor UPM alarm
•
Low pressure sensor UPM alarm
•
High pressure sensor UPM alarm
•
Condensate overflow UPM alarm
•
High/low voltage UPM alarm