Carrier Omnizone 50BVC Installation, Start-Up, Service And Controls Operation And Troubleshooting page 87

Water-cooled indoor self-contained systems
Table of Contents

Advertisement

PROTOCOL MAP
READ/
DISPLAY NAME
WRITE
RAT Reset Selec-
Holding Regis-
R/W
tion
Input Register
RAT Select
R
RAT SENS FAIL
R
Discrete Input
RAT_HI
R
Discrete Input
Reset Fan Rntm
R/W
Return Air Fan min
Holding Regis-
R/W
speed
Return Fan Output
R
Discrete Input
Cmd
Rev Valve Output
R
Discrete Input
Cmd
RF Overload
R
Discrete Input
RF Overload Status
R
Discrete Input
Holding Regis-
RH Sensor Sel
R/W
SA Static Press
Holding Regis-
R/W
High Trip
SA_CFG
R
Discrete Input
SA_SENS_FAIL
R
Discrete Input
SAS_HI
R
Discrete Input
Smk Det Alarm
R
Discrete Input
Smoke Detector
R
Discrete Input
Status
Static Shutdown
R
Discrete Input
Table 66 — Integration Points List (cont)
MODBUS
REGISTER
REGISTER
REFERENCE
TYPE
NUMBER
NAME
35
rat_sel
ter (Float)
35
rat_sel_sta
(Float)
59
rat_sen
60
rat_hi
Coil
10
fan_rntm_rst
raf_min_-
63
ter (Float)
speed
73
rtn_fan_cmd
61
rev_vlv_cmd
rblwr_ovr-
74
load_alm
rtn_blw_ovr-
75
load_status
rh_sensor_-
37
ter (Float)
39
sa_sta_hi_trip
ter (Float)
sa_config_er-
62
63
sas_sen
64
sas_hi
65
smoke
66
smoke_status
sa_stc_sht-
77
dwn
BACNET
OBJECT
OBJECT
TYPE
ID
AV
73
AV
78
BV
73
BV
78
BV
19
AV
166
BV
82
BV
15
BV
86
BV
98
AV
57
sel
AV
54
BV
90
ror
BV
65
BV
64
BV
89
BV
87
BV
16
87
LONWORKS
NV NAME
SNVT
Network Parameter to
set Return Air Tempera-
ture Selection
Select
0 = Hardwired Sensor
(Default)
1 = BAS Sensor Value
Network Parameter to
set Return Air Tempera-
ture Select
Select
0 = Single RAT Value
1 = Multiple RAT Values
(Default)
Return Air Temperature
Sensor Alarm
Select
0 = Normal
1 = Sensor Failure
(Check Sensor)
Return Air Temperature
Sensor Alarm
Select
0 = Normal
1 = Sensor Value >
120°F
Reset Fan Runtime.
Momentary On/Off
Select
required. Toggled upon
filter change.
Network Parameter to
set Return Air Tempera-
ture fan min speed
Select
0 = Single min Value
1 = Multiple min Values
(Default)
Network Parameter to
nvoRtn-
set the return air fan min-
SNVT_switch(95)
FanCmd
imum speed
40% (Factory Default)
Network Status of the
Select
Rev valve output
Network Alarm indicat-
ing return fan motor over-
Select
load trip
0 = Normal
1 = Overload Alarm
Network Status indicat-
ing return fan motor over-
Select
load trip
0 = Normal
1 = Overload Alarm
Network Parameter to
set RH sensor
Select
0 = Single sensor Value
1 = Multiple sensor Val-
ues (Default)
Network Parameter to
set the high static pres-
Select
sure trip point
Default 3.0 " of H2O
Network Alarm indicat-
Select
ing Smoke detector con-
figuration Error
Network Status Indicat-
ing Supply Static Pres-
Select
sure Sensor Failure
0 = Normal
1 = Sensor Failed
Static Air Pressure Alarm
(High)
nvoSasHi
SNVT_switch(95)
0 = Normal
1 = High Static Pressure
(Default: 3.0" H20)
Smoke Detector Alarm
nvoSmoke
SNVT_switch(95)
0 = Normal
1 = Alarm
Network Status of
Smoke Detector
Select
0 = Normal
1 = Smoke Alarm
Network Alarm indicat-
ing return high supply
Select
duct static
0 = Normal
1 = High Static Alarm