Table 23 — VFD Factory Default Settings (cont)
ABB 550 DRIVE FACTORY CONFIGURATION VFD 1
DESCRIPTION
3006
Motor Thermal Time
3007
Motor Load Curve
3008
Zero Speed Load
3009
Break Point Frequency
3010
Stall Function
3011
Stall Frequency
3012
Stall Time
3017
Earth Fault
3101
Number of Retries
3102
Trial Time
3103
Delay Time
3104
AR Overcurrent
3105
AR Overvoltage
3106
AR Undervoltage
3107
AR AI<Minimum
3108
AR External Fault
3401
Signal Parameter 1
3402
Signal 1 Minimum
3403
Signal 1 Maximum
3404
Output 1 DPS Form
3405
Output 1 DSP Unit
3406
Output 1 Minimum
3407
Output 1 Maximum
3408
Signal Parameter 2
3409
Signal 2 Minimum
3410
Signal 2 Maximum
3411
Output 2 DPS Form
3412
Output DSP Unit
3413
Output 2 Minimum
3414
Output 2 Maximum
3415
Signal Parameter 3
3416
Signal 3 Minimum
3417
Signal 3 Maximum
3418
Output 3 DPS Form
3419
Output DSP Unit
3420
Output 3 Minimum
3421
Output 3 Maximum
4001
4002
Integration Time
4005
Error Value Inver
4006
4007
Display Format
4010
Setpoint Select
4012
Setpoint Minimum
4013
Setpoint Maximum
4027
PID1 Parameter Set
60 / 50 (Maximum motor operating Hertz)
Current (Motor Current Measured by the Drive)
Gain
Units
46
VALUE
1050s
100%
70%
35Hz
NOT SEL
20 Hz
20 Sec
Enabled
5
30Sec
6 Sec
Enabled
Enabled
Enabled
Disabled
(0) Disabled
Output Freq
0
0
% SP
0
100
0
FLA + 15% A
0
A (2)
0
FLA + 15% A
AI-1
0
10
0
V (2)
0
10
2.5
3Sec
NO
%
x.xxx
Internal
0V
10V
SET1