PROTOCOL MAP
READ/
DISPLAY NAME
WRITE
Eff HGR Mod Valve
Input Register
R
1
Input Register
Eff RA Fan Speed
R
Eff RA Static Pres-
Input Register
R
sure
Input Register
Eff SA Fan Speed
R
Eff SA Static Pres-
Input Register
R
sure
Input Register
Eff Zone CO2 Lev
R
Input Register
Effect EW Temp
R
Effect Leaving Wtr
Input Register
R
Temp
Effect Outdoor Air
Input Register
R
Temp
ELW_SENS_FAIL
R
Discrete Input
Input Register
Enabled Stages
R
Factory Test
R/W
Input Register
Fan Mode Status
R
Fan Output Cmd
R
Discrete Input
Holding Regis-
Fan_mode
R/W
FILTER
R
Discrete Input
FRE
R
Discrete Input
FRE2
R
Discrete Input
High Static Count
R/W
Rst
HP1
R
Discrete Input
Table 66 — Integration Points List (cont)
MODBUS
REGISTER
REGISTER
REFERENCE
TYPE
NUMBER
NAME
eff_hgr_-
15
(Float)
mod_vlv1
eff_ra_fan_-
45
(Float)
speed
eff_ra_sta_-
47
(Float)
press
eff_sa_fan_-
17
(Float)
speed
eff_sa_sta_-
19
(Float)
press
eff_zn_-
21
(Float)
co2_lev
23
eff_ewt
(Float)
25
eff_lwt
(Float)
27
eff_rat
(Float)
38
elw_sen
enabled_cl-
29
(Float)
stages
fac_test_en-
Coil
14
able
fan_-
31
(Float)
mode_status
39
fan_cmd
19
fan_mode
ter (Float)
40
filter
41
frz_2st
42
frz_4st
rtn_sup_st-
Coil
23
c_ctr_rst
43
hp1_2st
BACNET
OBJECT
OBJECT
NV NAME
TYPE
ID
nvoEffHgr-
AV
28
ModVlv1
nvoEffRa-
AV
162
FanSpeed
nvoEffRa-
AV
163
StaPress
nvoEffSa-
AV
55
FanSpeed
nvoEffSa-
AV
53
StaPress
nvoEffZn-
AV
25
Co2Lev
AV
62
nvoEffEwt
AV
11
nvoEffLwt
AV
75
nvoEffRat
BV
72
AV
68
BV
91000
AV
51
BV
17
AV
50
BV
40
BV
8
BV
56
BV
99
nvoHp1Ala
BV
5
rm
84
LONWORKS
OPERATION
SNVT
DESCRIPTION
Hot Gas Reheat Modu-
SNVT_lev_per-
lating Valve Output Sta-
cent(81)
tus in %
SNVT_lev_per-
Supply Air Fan Speed
cent(81)
Network Status in %
Network Status of the
SNVT_count_inc(
Supply Duct Static Pres-
9)
sure Sensor
SNVT_lev_per-
Supply Air Fan Speed
cent(81)
Network Status in %
Network Status of the
SNVT_-
Supply Duct Static Pres-
press_p(113)
sure Sensor
Network Status of the
SNVT_count_inc(
CO
2
Sensor Levels in
9)
PPM
Network Status of the
SNVT_-
Entering Water Tem-
temp_p(105)
perature in °F
Network Status of the
SNVT_-
Entering Water Tem-
temp_p(105)
perature in °F
Network Status of the
SNVT_-
Return Air Temperature
temp_p(105)
in °F
Network Parameter to
set ELW sensor FAIL
Select
0 = Hardwired Sensor
(Default)
1 = BAS Sensor Value
Network Status of the
Select
number of Compressor
Stages Enabled
Factory Reserved
Select
Network Status of the
Fan Mode Selection
0 = Start / Stop Fan
Select
Operation
1 = Variable Frequency
Drive Fan Operation
Network Parameter to
set Fan Output Cmd
Select
0 = Hardwired Sensor
(Default)
1 = BAS Sensor Value
Network Parameter to
set Fan Mode of Opera-
tion
1 = Standard Fan Config-
Select
uration
2 = Variable Frequency
Drive Configuration (VAV
Default)
Filter Status
Select
0 = Normal
1 = Clean Filter
UPM Board 1 Freeze
Alarm
Select
0 = Normal
1 = Active Freeze Condi-
tion
UPM Board 2 Freeze
Alarm
Select
0 = Normal
1 = Active Freeze Condi-
tion
Network Parameter to
reset the high static
Select
alarm counter Momen-
tary toggle ON/OFF to
reset counter
UPM Board 1 High Pres-
sure Alarm Status for
Compressor 1
SNVT_switch(95)
0 = Normal
1 = Active High Pressure
1 Alarm