Troubleshooting - Fluke VIBGUARD IIoT Installation And Operation Manual

Hide thumbs Also See for VIBGUARD IIoT:
Table of Contents

Advertisement

Installation and Operation

9 Troubleshooting

The following errors may occur during operation:
Symptom: Sensor status LED on the system module indicates a fault message (flashing orange).
Possible cause: Sensor line is interrupted or has short circuited.
l
Remedy: Check that the connections on the sensor and system are secure. Exchange any damaged cables
l
or
Remedy: Check the cable connections with the PRÜFTECHNIK installation checker (item no. VIB 8.745).
l
Proceed as follows:
Use a cable with banana plugs and alligator clips to connect the sensor cable to the input terminals (1).
l
The three status LEDs on the housing indicate the condition of the sensor cable:
l
Green LED: OK
Red LED: Short circuit
Yellow LED: Ground loop
If none of the LEDs illuminate during testing and the battery is known to be fresh, then the sensor connection is bro-
ken. The installation checker is powered by a 9V battery. Battery condition can be checked as follows:
Connect the 'BATT. TEST' and 'GROUND' terminals (2)).
l
If the yellow LED illuminates, then battery voltage is below 5 volts and is no longer sufficient for reliable tes-
ting.
PRÜFTECHNIK-installation checker, VIB 8.745
Symptom: The SYSTEM LED on the system module does not light up.
Possible cause: Supply voltage is not applied.
l
Remedy: Connect to supply voltage.
l
or
50
Edition: 03.2019