Possible cause: Supply voltage parameters out of specification.
l
Remedy: Provide suitable supply voltage.
l
or
Possible cause: No output voltage generated by power supply unit.
l
Remedy: Replace power supply unit.
l
Proceed as follows to remove the defective power supply unit:
Push in the locking lever and pull the power supply unit (1T1) upwards.
l
or
Possible cause: Unknown fault on the system module.
l
Remedy: It is not possible to troubleshoot the system module directly. In the event of a malfunction, the sys-
l
tem module must be sent to the manufacturer.
Proceed as follows to remove the system module:
Disconnect the green terminal connectors from the system module to which cables are connected.
l
Remove the system module from the top hat rail.
l