To connect an open ended Ethernet cable to the terminal block, proceed as follows:
Open the cable gland (M12) for the Ethernet cable with a suitable open-end wrench (size 16) and remove
l
the seal
Insert the open cable end through the cable gland (3 – 6.5 mm).
l
Strip the 4 wires using a stripping tool for Ethernet cables (Tx-, Tx+, Rx-, Rx+)..
l
Braid or twist the screen into a wire.
l
If necessary, insulate exposed screen with shrink tubing. The screen must not come into direct contact with
l
the protective housing or other conductive components.
Crimp suitable wire end ferrules on the wire ends.
l
Connect the wires according to the following schema
l
Re-tighten the cable gland.
l
VIBGUARD IIoT
Connection for Ethernet cable (RJ45)
Ethernet connection via terminal block
Terminal
8
9
10
11
12
Installation and Operation
Designation Wire color
TX+
orange/white
TX-
orange
RX+
gree/white
RX-
green
PE-LAN
Screen
33