Fluke VIBGUARD IIoT Installation And Operation Manual page 47

Hide thumbs Also See for VIBGUARD IIoT:
Table of Contents

Advertisement

#5: CLD-type sensor via twisted pair cable
System module
VIB 7.820
VIB 7.825
Note: Cables with no signal on their screen must be insulated on the sensor side.
VIBGUARD IIoT
Terminal
49 to 96
49 to 72
Example for channel AI1
Terminal 49: Signal (+)
l
Terminal 50: GND (-).
l
Terminal 51: Screen (S).
l
Prepare the cable screen with the shield connection set (VIB
6.725-100).
CLD-type sensor VIB 6.195 with sensor cable, e.g. VIB 3.570-6.
Installation and Operation
Instructions
Signal to plus (+),
l
GND to minus (-),
l
Connect screen to screen terminal (S).
l
47