Table 3-10 Datacorder Pre-Trip Data - Carrier 69NT40-511-1 Operating And Service Manual

Container refrigeration unit
Hide thumbs Also See for 69NT40-511-1:
Table of Contents

Advertisement

TEST #
TITLE
"Auto" or "Auto1" menu includes the following: P, P1, P2, P3, P4, P5, P6 and rSLts. "Auto2' (Optional)
menu includes the following: P, P1, P2, P3, P4, P5, P6,P7, P8, P9, P10 and rSLts. (Refer to section 3.2.1.)
1-0
Heater On
1-1
Heater Off
2-0
Condenser Fan On
2-1
Condenser Fan Off
3-0
Low Speed Evaporator Fan
On
3-1
Low Speed Evaporator Fan
On
4-0
High Speed Evaporator Fan
On
4-1
High Speed Evaporator Fan
On
5-0
Supply/Return Probe Test
5-1
Secondary Supply Probe Test
5-2
Secondary Return Probe Test
6-0
Compressor On -- High Speed Pass/Fail/Skip Result, Change in currents for Phase A, B and C
6-1
Compressor On -- Low Speed
6-2
Suction Modulation Valve
Open
6-4
Suction Modulation Valve
Closed
6-5
Suction Solenoid Valve Open
7-0
High Pressure Switch Closed
7-1
High Pressure Switch Open
8-0
Perishable Heat
8-1
Perishable Pull Down
8-2
Perishable Maintain
9-0
Defrost Test
10-0
Frozen Mode Set-up
10-1
Frozen Mode Pull Down
10-2
Frozen Mode Maintain
Table 3-10. DataCORDER Pre-Trip Data
NOTE
Pass/Fail/Skip Result, Change in current for Phase A, B and C
Pass/Fail/Skip Result, Change in currents for Phase A, B and C
Pass/Fail/Skip Result, Water pressure switch (WPS) -- Open/Closed,
Change in currents for Phase A, B and C
Pass/Fail/Skip Result, Change in currents for Phase A, B and C
Pass/Fail/Skip Result, Change in currents for Phase A, B and C
Pass/Fail/Skip Result, Change in currents for Phase A, B and C
Pass/Fail/Skip Result, Change in currents for Phase A, B and C
Pass/Fail/Skip Result, Change in currents for Phase A, B and C
Pass/Fail/Skip Result, STS, RTS, SRS and RRS
Pass/Fail/Skip Result
Pass/Fail/Skip Result
Pass/Fail/Skip Result, Change in currents for Phase A, B and C
Pass/Fail/Skip Result, STS, RTS, Is current limit in effect? (Y,N)?
Pass/Fail/Skip Result, STS, RTS, Delta T1, Delta T2,
Is current limit in effect? (Y,N)?
Pass/Fail/Skip Result, STS, RTS, Is current limit in effect? (Y,N)?
Pass/Fail/Skip Result, AMBS, DPT or CPT (if equipped)
Input values that component opens?
Pass/Fail/Skip Result, STS, DPT or CPT (if equipped)
Input values that component closes?
Pass/Fail/Skip Result, STS, time it takes to heat to 16_C (60_F)?
Pass/Fail/Skip Result, STS, time it takes to pull down to 0_C (32_F)?
Pass/Fail/Skip Result, Averaged DataCORDER supply temperature
(SRS) over last recording interval.
Pass/Fail/Skip Result, DTS temperature at end of test, line voltage,
line frequency, time in defrost.
Pass/Fail/Skip Result, STS, time unit is in heat.
Pass/Fail/Skip Result, STS, time to pull down unit to --17.8_C (0_F).
Pass/Fail/Skip Result, Averaged DataCORDER return temperature
(RRS) over last recording interval.
3-33
DATA
T-268-07