Water-Cooled Condenser - Carrier 69NT40-511-1 Operating And Service Manual

Container refrigeration unit
Hide thumbs Also See for 69NT40-511-1:
Table of Contents

Advertisement

circuits (refer to section 5). A description of the test
points follows:
NOTE
Use a digital voltmeter to measure ac voltage
between TP's and ground (TP9), except for
TP8.
TP2
This test point enables the user to check if the internal
protector for the compressor motor (IP-CP) is open or
closed (and the Auto Transformer-IP if so equipped).
TP3
This test point enables the user to check if the optional
water pressure switch (WP) contact is open or closed.
TP7
This test point enables the user to check if the Controller
relay (TS) contact is open or closed.
TP8
This test point enables the user to check the suction
modulation valve (SMV) current (amps), it is
represented by twice the dc volts between TP8 and TP9.
TP9
This test point is the chassis (unit frame) ground
connection.

6.28 WATER-COOLED CONDENSER

The water-cooled condenser is of the shell and coil type
with water circulating through the cupro-nickel coil.
The refrigerant vapor is admitted to the shell side and is
condensed on the outer surface of the coil.
Rust, scale and slime on the water-cooling surfaces
inside of the coil interfere with the transfer of heat,
reduce system capacity, cause higher head pressures
and increase the load on the system.
By checking the leaving water temperature and the
actual condensing temperature, it can be determined if
the condenser coil is becoming dirty. A larger than
normal difference between leaving condensing water
temperature and actual condensing temperature,
coupled with a small difference in temperature of
entering and leaving condensing water, is an indication
of a dirty condensing coil.
To find the approximate condensing temperature, with
the unit running in the cooling mode, install a gauge 0 to
36.2 kg/cm@ (0 to 500 psig) on the compressor
discharge service valve.
T-268-07
Example: Discharge pressure is 10.3 kg/cm@ (146.4
psig).
Referring
pressure-temperature chart), the 10.3 kg/cm@ (146.4
psig) value converts to 43_C (110_F).
If the water-cooled condenser is dirty, it may be cleaned
and de-scaled by the following procedure:
a. Turn unit off and disconnect main power.
b. Disconnect water pressure switch tubing by
loosening the two flare nuts. Install one-quarter
inch flare cap on water-cooled condenser inlet tube
(replaces tubing flare nut). De-scale tubing if
necessary.
What You Will Need:
1. Oakite composition No. 22, available as a powder
in 68 kg (150 lb) and 136 kg (300 lb).
2. Oakite composition No. 32, available as a liquid in
cases, each containing 3.785 liters (4 U.S. gallon)
bottles and also in carboys of 52.6 kg (116 lbs) net.
3. Fresh clean water.
4. Acid proof pump and containers or bottles with
rubber hose.
When Oakite compound No. 32 is being used
for the first time, the local Oakite Technical
Service representative should be called in for
their suggestions in planning the procedure.
They will show you how to do the work with a
minimum dismantling of equipment: how to
estimate the time and amount of compound
required; how to prepare the solution; how to
control and conclude the de-scaling operation
by rinsing and neutralizing equipment before
putting it back into service. Their knowledge of
metals, types of scale, water conditions and
de-scaling techniques will be highly useful to
you.
Summary of Procedure:
1. Drain water from condenser tubing circuit. Clean
water tubes with Oakite No. 22 to remove mud and
slime.
2. Flush.
3. De-scale water tubes with Oakite No. 32 to remove
scale.
4. Flush.
5. Neutralize.
6. Flush.
6-30
to
Table 6-6
(R-134a
NOTE