Carrier 69NT40-511-1 Operating And Service Manual page 60

Container refrigeration unit
Hide thumbs Also See for 69NT40-511-1:
Table of Contents

Advertisement

CODE
TITLE
#
Starting with test P7-0 through test P10, these tests are only included with the "Auto2" (Optional) selection
menu. (Refer to section 3.2.1.)
High Pressure
High Pressure
P7 0
P7-0
Switch Closed
High Pressure
P7-1
Switch Open
Perishable Mode
P8-0
Heat Test
T-268-07
NOTE
Setup: When the unit is running, the condenser fan is de-energized, and a 15
minute timer is started. The right display shows discharge pressure if equipped
with the discharge pressure transducer (DPT), or condenser pressure if
equipped with a condenser pressure transducer (CPT), or discharge pressure if
equipped with either a discharge pressure transducer (DPT) or a condenser
pressure transducer (CPT).
Pass/Fail Criteria: The test fails if high pressure switch fails to open in 900
seconds.
Note, this test is skipped if the unit does NOT have:
A compressor discharge sensor (CPDS).
S
A discharge pressure transducer (DPT).
S
Condenser pressure transducer (CPT).
S
In addition, this test is skipped if:
The sensed ambient temperature is less than 7_C (45_F).
S
The return air temperature is less than - -17.8_C (0_F).
S
The water pressure switch (WP) is open, indicating that the unit is
S
operating with a water-cooled condenser.
Pass/Fail Criteria: Under conditions of the above Note, the test immediately
fails if the following inputs are sensed to be invalid:
Compressor discharge sensor (CPDS).
S
Discharge pressure transducer (DPT).
S
Condenser pressure transducer (CPT).
S
OR if any one of the following inputs are sensed to be invalid:
Return temperature sensor (RTS).
S
Ambient sensor (AMBS).
S
In addition, the test will fail if:
The high pressure switch (HPS) fails to open within 15 minutes.
S
The discharge temperature exceeds 138_C (280_F).
S
The discharge temperature is less than or equal to ambient temperature
S
plus 5_C (9_F).
The condenser pressure transducer (CPT) or discharge pressure
S
transducer (DPT) pressure exceeds 27.42 kg/cm
Requirements: Test P7-0 must pass for this test to execute. Setup: The
condenser fan is started and a 60 second timer is started.
Pass/Fail Criteria: Passes the test if the high pressure switch (HPS) closes
within the 60 second time limit, otherwise, it fails.
Setup: If the container temperature is below 60_F, the set point is changed to
60_F, and a 60 minute timer is started. The left display will read "P8-0." The
control will then heat the container until 60_F is reached. If the container
temperature is above 60_F at the start of the test, then the test proceeds
immediately to test P8-1 and the left display will change to "P8-1."
Pass/Fail Criteria: The test fails if the 180 minute timer expires before the
control temperature reaches set point. The display will read "P8--0," "FAIL."
3-22
DESCRIPTION
2
(390 psig).