Summary of Contents for Endress+Hauser Proline Promag W 800
Page 1
Products Solutions Services BA02080D/06/EN/02.22-00 71551482 2022-01-15 Valid as of version 01.00.zz (Device firmware) Operating Instructions Proline Promag W 800 Electromagnetic flowmeter Cellular radio (Type: DA800C-CRM02.01)
Page 2
• The manufacturer reserves the right to modify technical data without prior notice. Your Endress+Hauser Sales Center will supply you with current information and updates to these instructions. Endress+Hauser...
Proline Promag W 800 Cellular radio About this document About this document Document function These Operating Instructions contain all the information that is required in various phases of the life cycle of the device: from product identification, incoming acceptance and storage, to mounting, connection, operation and commissioning through to troubleshooting, maintenance and disposal.
About this document Proline Promag W 800 Cellular radio 1.2.4 Tool symbols Symbol Meaning Torx screwdriver Flat-blade screwdriver Phillips head screwdriver Allen key Open-ended wrench 1.2.5 Symbols for certain types of information Symbol Meaning Permitted Procedures, processes or actions that are permitted.
• W@M Device Viewer (www.endress.com/deviceviewer): Enter the serial number from the nameplate • Endress+Hauser Operations App: Enter the serial number from the nameplate or scan the matrix code on the nameplate Detailed list of the individual documents along with the documentation code →...
Safety instructions Proline Promag W 800 Cellular radio Safety instructions Requirements for the personnel The personnel for installation, commissioning, diagnostics and maintenance must fulfill the following requirements: ‣ Trained, qualified specialists must have a relevant qualification for this specific function and task.
Verification for borderline cases: ‣ For special fluids and fluids for cleaning, Endress+Hauser is glad to provide assistance in verifying the corrosion resistance of fluid-wetted materials, but does not accept any warranty or liability as minute changes in the temperature, concentration or level of contamination in the process can alter the corrosion resistance properties.
Safety instructions Proline Promag W 800 Cellular radio By selecting the order option for UKCA marking, Endress+Hauser confirms a successful evaluation and testing of the device by affixing the UKCA mark. Contact address Endress+Hauser UK: Endress+Hauser Ltd. Floats Road Manchester M23 9NF United Kingdom www.uk.endress.com...
Page 11
Proline Promag W 800 Cellular radio Safety instructions Write protection via write protection switch Off A0047361 ‣ Information regarding the write protection switch is provided on the connection nameplate in the connection compartment cover. Unlike parameter write protection via a user-specific access code, this allows write access to the entire operating menu to be locked.
Safety instructions Proline Promag W 800 Cellular radio 2.7.3 Access via Bluetooth® wireless technology Secure signal transmission via Bluetooth® wireless technology uses an encryption method tested by the Fraunhofer Institute. • The device is not visible via Bluetooth® wireless technology without the SmartBlue App.
Proline Promag W 800 Cellular radio Product description Product description The device consists of a transmitter and a sensor. Proline Promag 800 Compact version - transmitter and sensor form a mechanical unit. Proline Promag 800 - Advanced Two device versions are available: •...
Is the envelope present with accompanying documents? • If one of the conditions is not satisfied, contact your Endress+Hauser Sales Center. • The Technical Documentation is available via the Internet or via the Endress+Hauser Operations App, see the "Product identification" section → 15.
"Supplementary device-dependent documentation" → 7 • The W@M Device Viewer: Enter the serial number from the nameplate (www.endress.com/deviceviewer) • The Endress+Hauser Operations App: Enter the serial number from the nameplate or scan the DataMatrix code on the nameplate. 4.2.1 Transmitter nameplate •...
Incoming acceptance and product identification Proline Promag W 800 Cellular radio 4.2.3 Symbols on measuring device Symbol Meaning WARNING! This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in serious or fatal injury. To determine the nature of the potential hazard and the measures required to avoid it, consult the documentation accompanying the measuring device.
Proline Promag W 800 Cellular radio Storage and transport Storage and transport Storage conditions Observe the following notes for storage: ‣ Store in the original packaging to ensure protection from shock. ‣ Do not remove protective covers or protective caps installed on process connections.
Storage and transport Proline Promag W 800 Cellular radio 4 → 2.5 Nm (1.8 lbf ft) A0043737 A0042855 ‣ ‣ Close the display module. Close the connection compartment cover. Transporting the product Transport the measuring device to the measuring point in the original packaging.
Proline Promag W 800 Cellular radio Mounting 5.3.2 Measuring devices with lifting lugs CAUTION Special transportation instructions for devices with lifting lugs ‣ Only use the lifting lugs fitted on the device or flanges to transport the device. ‣ The device must always be secured at two lifting lugs at least.
Page 20
Mounting Proline Promag W 800 Cellular radio A0042131 The device should ideally be installed in an ascending pipe. A0042317 Installation near valves Install the device in the direction of flow upstream from the valve. A0041091 Installation upstream from a down pipe...
Page 21
Proline Promag W 800 Cellular radio Mounting Installation with partially filled pipes • Partially filled pipes with a gradient require a drain-type configuration. • The installation of a cleaning valve is recommended. A0041088 No inlet and outlet runs for devices with the order code for "Design": Option C.
Page 22
Mounting Proline Promag W 800 Cellular radio Installation in event of pipe vibrations A remote version is recommended in the event of strong pipe vibrations. NOTICE Pipe vibrations can damage the device! ‣ Do not expose the device to strong vibrations.
Page 23
Proline Promag W 800 Cellular radio Mounting Vertical Optimum for self-emptying pipe systems and for use in conjunction with empty pipe detection. A0015591 Horizontal • Ideally, the measuring electrode plane should be horizontal. This prevents brief insulation of the measuring electrodes by entrained air bubbles.
Page 24
Mounting Proline Promag W 800 Cellular radio A0042132 Installation without inlet and outlet runs Depending on the device design and installation location, the inlet and outlet runs can be reduced or omitted entirely. Maximum measured error When the device is installed with the inlet and outlet runs described, a maximum measured error of ±0.5 % of the reading ±2 mm/s (0.08 in/s) can be guaranteed.
Proline Promag W 800 Cellular radio Mounting Dimensions For the dimensions and installed lengths of the device, see the "Technical Information" document, "Mechanical construction" section 6.1.2 Environment and process-related requirements Ambient temperature range Transmitter –25 to +60 °C (–13 to +140 °F) Local display –20 to +60 °C (–4 to +140 °F), the readability of the local display may be...
Page 26
Mounting Proline Promag W 800 Cellular radio [mbar] 8 m/s 7 m/s 6 m/s 5 m/s 4 m/s 3 m/s max. 8° 2 m/s 1 m/s d / D A0029002 Length of connecting cable To obtain correct measurement results, observe the permitted connecting cable length of .
Proline Promag W 800 Cellular radio Mounting 6.1.3 Special mounting instructions Display guard ‣ To ensure that the display guard can be easily opened, maintain the following minimum head clearance: 350 mm (13.8 in) External cellular antenna, Proline 800 - Advanced ‣...
Mounting Proline Promag W 800 Cellular radio For use in buried applications, Proline 800 - Advanced • Only the remote version of the device with IP68 protection is suitable for use in buried applications: order code for "Sensor option", options CD and CE.
Page 29
Proline Promag W 800 Cellular radio Mounting 1. Ensure that the direction of the arrow on the sensor matches the flow direction of the medium. 2. To ensure compliance with device specifications, install the measuring device between the pipe flanges in a way that it is centered in the measurement section.
Page 35
Proline Promag W 800 Cellular radio Mounting CAUTION Excessive force can damage the housing! ‣ Avoid excessive mechanical stress. The transmitter of the remote version can be mounted in the following ways: • Wall mounting • Pipe mounting Wall mounting Proline 800 - Advanced 17 (0.67)
Mounting Proline Promag W 800 Cellular radio ø TX 25 20…70 ø ( 0.79…2.75) SW 10 A0029051 5 Engineering unit mm (in) 6.2.5 Turning the transmitter housing, Proline 800 - Advanced To provide easier access to the connection compartment or display module, the transmitter housing can be turned.
Page 37
Proline Promag W 800 Cellular radio Mounting A0044273 6. Push the display module down gently at the hinge. 7. Pull the display module out of the holder. A0043338 8. Disconnect the plug of the electronics module. 1 Nm (0.7 lbf ft) A0042853 9.
Page 38
Mounting Proline Promag W 800 Cellular radio TX 20 A0044276 11. Loosen the fixing screws of the main electronics module (when reassembling, pay attention to the tightening torque → 38). 12. Remove the main electronics module. 4 mm A0044277 13.
Proline Promag W 800 Cellular radio Mounting A0044279 ‣ Reverse the procedure to reassemble the measuring device. 6.2.6 Mounting the external cellular antenna If the signal is too weak, mount the external cellular antenna in a separate location. TX 15...
Proline Promag W 800 Cellular radio 6.2.8 Inserting the SIM card The device is equipped with an Endress+Hauser eSIM. The device automatically recognizes an additional SIM card that has been inserted. The additionally inserted SIM card may not be protected by a PIN.
Page 41
Proline Promag W 800 Cellular radio Mounting Is the device adequately protected from precipitation and direct sunlight? Have the fixing screws been tightened with the correct tightening torque? Endress+Hauser...
Electrical connection Proline Promag W 800 Cellular radio Electrical connection NOTICE In the device versions with a mains connection (order code for "Power supply" option K or S), the device does not have an internal circuit breaker to disconnect from the power supply network.
Proline Promag W 800 Cellular radio Electrical connection Capacitance: core/core, ≤120 pF/m (37 pF/ft) shield grounded Operating temperature –25 to +70 °C (–13 to +158 °F) Test voltage for cable ≤ AC 1433 V rms 50/60 Hz or ≥ DC 2026 V...
Electrical connection Proline Promag W 800 Cellular radio 7.2.5 Requirements for the supply unit Supply voltage Order code Terminal numbers Terminal voltage Frequency range "Power supply" Option K DC 24 V –20 to +25 % – Option S 1 (L+/L), 2 (L-/N) AC 100 to 240 V –15 to +10 %...
Page 47
Proline Promag W 800 Cellular radio Electrical connection Transmitter Electrode cable Coil current cable (3.54) 100 (3.94)* 70 (2.76) 80 (3.15) 50 (1.97) 50 (1.97) 17 (0.67) 8 (0.31) 10 (0.39) 8 (0.31) A0032096 9 Engineering unit mm (in) A0032093 ...
Page 49
Proline Promag W 800 Cellular radio Electrical connection Connecting the connecting cable to the sensor connection housing 42 41 A0032103 10 Sensor: connection module 1. Loosen the securing clamp of the housing cover. 2. Unscrew and lift off the housing cover.
Electrical connection Proline Promag W 800 Cellular radio Attaching the connecting cable to the transmitter 6 5 7 8 4 37 36 42 41 A0044280 11 Transmitter: main electronics module with terminals 1. Loosen the 4 fixing screws on the housing cover.
Proline Promag W 800 Cellular radio Electrical connection T 20 22232021 26272425 10 (0.4) A0044281 12 Connecting the supply voltage 1. Loosen the 4 fixing screws on the housing cover. 2. Open the housing cover. 3. Push the cable through the cable entry. To ensure tight sealing, do not remove the sealing ring from the cable entry.
Page 52
Electrical connection Proline Promag W 800 Cellular radio The following requirements must be observed to ensure correct, trouble-free measurement: • The principle that the medium, the sensor and the transmitter must be at the same electrical potential applies. • Take in-company grounding guidelines, materials and the grounding conditions and potential conditions of the pipe into consideration.
Page 53
Proline Promag W 800 Cellular radio Electrical connection DN 300 DN 350 ≥ ≤ PE = P A0042089 1. Connect both sensor flanges to the pipe flange via a ground cable and ground them. 2. Connect the connection housing of the transmitter or sensor to ground potential via the ground terminal provided for this purpose.
Electrical connection Proline Promag W 800 Cellular radio Metal, ungrounded pipe The sensor and transmitter are installed in a way that provides electrical insulation from PE, e.g. applications for electrolytic processes or systems with cathodic protection. Starting conditions: • Unlined metal pipe •...
Proline Promag W 800 Cellular radio Electrical connection 7.4.2 Inserting and connecting buffer capacitors and battery packs The device is delivered either with the batteries already installed, or enclosed separately, depending on national standards and guidelines. If the batteries are inserted and connected upon delivery, to operate the device it is important to ensure that switch "B"...
Electrical connection Proline Promag W 800 Cellular radio 8 → 9 → A0043732 A0043733 ‣ ‣ Insert battery packs 1 and 2. Plug the connector of battery pack 1 into connector 1. ‣ Plug the connector of battery pack 2 into connector 2.
Proline Promag W 800 Cellular radio Electrical connection 3 → A0044324 ‣ Guide the cable of the cellular antenna through the cable gland indicated. ‣ Connect the cable of the cellular antenna to the cable of the antenna connector. 2.5 Nm (1.8 lbf ft)
Electrical connection Proline Promag W 800 Cellular radio Power supply via the external battery pack, Proline 800 - Advanced 7.7.1 Connecting the external battery pack A0044313 Plug for the external battery pack ‣ Connect the external battery pack to the plug indicated.
Proline Promag W 800 Cellular radio Electrical connection Special connection instructions 7.8.1 Connection examples Pulseoutput 12345 A0044387 13 Connection example for pulse output (passive) Automation system with pulse input (e.g. PLC) External DC power supply (e.g. 24 VDC) Open collector pulse input of the transmitter: observe input values Pull-up resistor (e.g.
Electrical connection Proline Promag W 800 Cellular radio To guarantee IP66/67 degree of protection, Type 4X enclosure, carry out the following steps after the electrical connection: 1. Check that the housing seals are clean and fitted correctly. Dry, clean or replace the seals if necessary.
• Device software update • Heartbeat report • Parameter report The SmartBlue app is available to download free of charge for Android devices (Google Playstore) and iOS devices (iTunes Apple Store): Endress+Hauser SmartBlue Directly to the app with the QR code: A0033202 Endress+Hauser...
Page 62
Operation options Proline Promag W 800 Cellular radio Downloading the SmartBlue app: 1. Install and start the SmartBlue app. A Live List shows all the devices available. The list displays the devices with the configured tag name. The default setting of the device tag is EH_5W8C_XXYYZZ (XXYYZZ = the first 6 characters of the device serial number).
Proline Promag W 800 Cellular radio System integration System integration Overview of device description files 9.1.1 Current version data for the device Firmware version 01.00.zz • On the title page of the Operating Instructions • On the transmitter nameplate • Firmware version Diagnostics →...
Commissioning Proline Promag W 800 Cellular radio Commissioning 10.1 Function check Before commissioning the measuring device: ‣ Make sure that the post-installation and post-connection checks have been performed. • "Post-installation check" checklist • "Post-connection check" checklist 10.2 Preparatory steps The device can only be operated via the SmartBlue App.
Proline Promag W 800 Cellular radio Commissioning 2. Open the User management submenu. 3. Open the Define access code wizard. 4. Define a string, consisting of up to 4 numbers, for the access code. The parameters are write-protected. • If parameter write protection is activated via an access code, it can also only be deactivated via this access code .
Page 66
Commissioning Proline Promag W 800 Cellular radio WARNING Excessive tightening torque applied to the securing screws! Risk of damaging the plastic transmitter. ‣ Tighten the securing screws as per the tightening torque . Reverse the removal procedure to reassemble the transmitter.
Proline Promag W 800 Cellular radio Operation Operation 11.1 Wake on Touch If you touch the display for 5 seconds the device displays measured values and status information. m /min A0043867 Locking status The device is locked via the hardware.
Operation Proline Promag W 800 Cellular radio 11.2 Adapting the measuring device to the process conditions To do so, users can choose from the following menus: • Guidance • Application Detailed information on "Guidance menu" and "Application menu": Device parameters →...
• Heartbeat Verification • Custody transfer • Heartbeat Monitoring 11.6 Updating the firmware Firmware updates are available in the Download Area of the Endress+Hauser website: www.endress.com → Downloads Specify the following details for the "Device driver": • Type: "Firmware Flash File"...
Diagnostics and troubleshooting Proline Promag W 800 Cellular radio Diagnostics and troubleshooting 12.1 General troubleshooting For local display Error Possible causes Remedial action Local display remains dark for Supply voltage does not match the Apply the correct supply voltage longer than 5 seconds when voltage specified on the nameplate.
Page 71
Proline Promag W 800 Cellular radio Diagnostics and troubleshooting For access Error Possible causes Remedial action No write access to parameters Hardware write protection enabled Set the write protection switch on the back of the display to the ON position → 11.
Diagnostics and troubleshooting Proline Promag W 800 Cellular radio 12.2 Diagnostic information on local display 12.2.1 Diagnostic message Faults detected by the self-monitoring system of the measuring device are displayed as a diagnostic message in alternation with the operational display.
Proline Promag W 800 Cellular radio Diagnostics and troubleshooting Diagnostic behavior Diagnostic message Meaning Alarm • The measurement is interrupted. • Signal outputs and totalizers assume the defined alarm condition. • A diagnostic message is generated. Function check Process measured values are simulated to test the outputs/wiring.
Page 74
Diagnostics and troubleshooting Proline Promag W 800 Cellular radio Diagnostic Short text Remedy instructions Status Diagnostic number signal behavior [from the [from the factory] factory] Diagnostic of sensor Data storage inconsistent 1. Check module connections Alarm 2. Contact service Memory content 1.
Page 75
Proline Promag W 800 Cellular radio Diagnostics and troubleshooting Diagnostic Short text Remedy instructions Status Diagnostic number signal behavior [from the [from the factory] factory] Memory content 1. Restart device Alarm 2. Delete T-DAT via ' R eset device' parameter 3.
Diagnostics and troubleshooting Proline Promag W 800 Cellular radio Diagnostic Short text Remedy instructions Status Diagnostic number signal behavior [from the [from the factory] factory] Electronics temperature Increase ambient temperature Warning too low Process value above limit Low flow cut off active! Warning 1.
Proline Promag W 800 Cellular radio Diagnostics and troubleshooting Timestamp → 77 Operating time from restart → 77 → 77 Operating time Parameter overview with brief description Parameter Description User interface Actual diagnostics Shows the current occured diagnostic event along with its Positive integer diagnostic information.
Diagnostics and troubleshooting Proline Promag W 800 Cellular radio In addition to the operation time of its occurrence, each event is also assigned a symbol that indicates whether the event has occurred or is ended: • Diagnostic event • : Occurrence of the event •...
Proline Promag W 800 Cellular radio Diagnostics and troubleshooting Info number Info name I1445 Device verification failed I1457 Measurement error verification failed I1459 I/O module verification failed I1461 Sensor verification failed I1462 Electronic module verification failed I1512 Download started I1513...
Diagnostics and troubleshooting Proline Promag W 800 Cellular radio Navigation "System" menu → Information → Device Parameter overview with brief description Parameter Description User interface Serial number Shows the serial number of the measuring device. Character string comprising numbers, letters...
Proline Promag W 800 Cellular radio Maintenance Maintenance 13.1 Maintenance tasks No special maintenance work is required. 13.1.1 Exterior cleaning When cleaning the exterior of measuring devices, always use cleaning agents that do not attack the surface of the housing or the seals.
Page 82
Maintenance Proline Promag W 800 Cellular radio Shut down device 1. Open System. 2. Open Device management. 3. Open Device reset. 4. Select Shut down device. 5. Press OK to confirm. As soon as F418 appears on the local display, the device can be disconnected from the power supply without any loss of data.
Page 83
The following lithium thyionyl chloride batteries are recommended by Endress +Hauser: • Tadiran SL2780 • Saft LS33600 • Eve ER34615 • Tadiran SL2880 The following alkaline batteries are recommended by Endress+Hauser: • Energizer E95 • Duracell MX1300 • Panasonic LR20XWA • Varta 4020 Endress+Hauser...
13.2 Measuring and test equipment Endress+Hauser offers a wide variety of measuring and test equipment, such as W@M or device tests. Your Endress+Hauser Sales Center can provide detailed information on the services. List of some of the measuring and testing equipment: → 88 13.3...
• The measuring devices have a modular design. • Spare parts are grouped into logical kits with the associated Installation Instructions. • Repairs are carried out by Endress+Hauser Service or by appropriately trained customers. • Certified devices can only be converted to other certified devices by Endress+Hauser Service or at the factory.
(WEEE), the product is marked with the depicted symbol in order to minimize the disposal of WEEE as unsorted municipal waste. Do not dispose of products bearing this marking as unsorted municipal waste. Instead, return them to Endress+Hauser for disposal under the applicable conditions.
Various accessories, which can be ordered with the device or subsequently from Endress +Hauser, are available for the device. Detailed information on the order code in question is available from your local Endress+Hauser sales center or on the product page of the Endress+Hauser website: www.endress.com.
• Access to measured values, device status and diagnostics information SmartBlue is available as download for Android devices from the Google Play Store and for iOS devices from the iTunes Store: Endress+Hauser SmartBlue Directly to the app with the QR code:...
Proline Promag W 800 Cellular radio Technical data Technical data 16.1 Application The measuring device is only suitable for the flow measurement of liquids with a minimum conductivity of 20 µS/cm. To ensure that the device remains in proper operating condition for its service life, use the measuring device only for media against which the process-wetted materials are sufficiently resistant.
Page 90
Technical data Proline Promag W 800 Cellular radio Nominal Recommended Factory settings diameter flow min./max. full scale value Pulse value Low flow cut off (v ~ 0.3/10 m/s) (~ 2 pulse/s) (v ~ 0.04 m/s) [mm] [in] 20 to 600 0.025...
Page 91
Proline Promag W 800 Cellular radio Technical data Nominal Recommended Factory settings diameter flow min./max. full scale value Pulse value Low flow cut off (v ~ 0.3/10 m/s) (~ 2 pulse/s) (v ~ 0.04 m/s) [in] [mm] [gal/min] [gal] [gal/min]...
Technical data Proline Promag W 800 Cellular radio 16.4 Output Output signal Status/pulse output Function With the order code for "Output; Input", option P: cellular radio, 3 outputs can be set either as a pulse output or switch output Version...
Proline Promag W 800 Cellular radio Technical data Interface/protocol Via digital communication: • SmartBlue App • Cellular radio Plain text display With information on cause and remedial measures Low flow cut off The switch points for low flow cut off are user-selectable.
Page 94
High-power lithium-thionyl chloride batteries are listed under Hazard Class 9: Miscellaneous Hazardous Materials. Observe the hazardous materials regulations described in the Safety Datasheet. The Safety Datasheet can be requested from any Endress+Hauser sales organization. Buffer capacitor specifications • Lithium hybrid layer capacitor •...
Page 95
Proline Promag W 800 Cellular radio Technical data Estimated battery lifetime A0040189 14 Operating principle of various data logging methods Flow profile Minimum measuring interval value (external power supply) Fixed measuring interval value between the sensor-dependent minimum and 60 seconds...
Page 96
Technical data Proline Promag W 800 Cellular radio • An active pulse output with 2 Hz @ 5 ms • Modbus transmission interval: 15 seconds • Ambient temperature: 25 °C (77 °F) The battery lifetime is significantly shortened by: • Shortening the EFM measuring interval •...
Proline Promag W 800 Cellular radio Technical data Terminals Spring terminals for wire cross-sections 0.5 to 2.5 mm (20 to 14 AWG) Cable entries Cable entry thread • NPT ½" • G ½" Cable gland • For standard cable: M20 × 1.5 with cable 6 to 12 mm (0.24 to 0.47 in) •...
Technical data Proline Promag W 800 Cellular radio Accuracy of outputs The outputs have the following base accuracy specifications. Pulse output o.r. = of reading Accuracy Max. ±50 ppm o.r. (over the entire ambient temperature range) Repeatability o.r. = of reading Volume flow Max.
Page 99
Proline Promag W 800 Cellular radio Technical data Degree of protection Transmitter • Standard: IP66/67, Type 4X enclosure, suitable for pollution degree 4 • When the housing is open: IP20, Type 1 enclosure, suitable for pollution degree 2 An inserted mating connector or a fitted protection cap is accepted as a prerequisite for maintaining the specified degree of protection.
Technical data Proline Promag W 800 Cellular radio Mechanical load • Protect the transmitter housing against mechanical effects, such as shock or impact; the use of the remote version is sometimes preferable. • Never use the transmitter housing as a ladder or climbing aid.
Page 101
Proline Promag W 800 Cellular radio Technical data Pressure-temperature For an overview of the pressure-temperature ratings for the process connections, see ratings the Technical Information Pressure tightness Liner: hard rubber Nominal diameter Limit values for absolute pressure in [mbar] ([psi]) for medium...
Technical data Proline Promag W 800 Cellular radio [psi] [mbar] DN50 DN65 (2") (2½") DN80 (3") [m /h] ³ 20 30 40 50 60 70 80 90 100 110 120 [gal/min] A0032667-EN 16 Pressure loss DN 50 to 80 (2 to 3") for order code for "Design", option C "Fixed flange, constricted measuring tube", 0 x DN inlet/outlet runs"...
Page 103
Proline Promag W 800 Cellular radio Technical data Weight All values (weight exclusive of packaging material) refer to devices with flanges of the standard pressure rating. The weight may be lower than indicated depending on the pressure rating and design.
Page 104
Technical data Proline Promag W 800 Cellular radio Weight in US units Order code for "Design", option C, D, E: DN 1 to 16 in (25 to 400 mm) Nominal diameter Reference values ASME (Class 150) [mm] [in] [lb] –...
Page 105
Proline Promag W 800 Cellular radio Technical data Nominal diameter Pressure rating Measuring tube internal diameter EN (DIN) ASME AS 2129 Hard rubber Polyurethane PTFE AS 4087 [mm] [in] [mm] [in] [mm] [in] [mm] [in] PN 40 Class 150 –...
Page 106
Technical data Proline Promag W 800 Cellular radio Materials Transmitter housing Compact version • Housing material: Polycarbonate • Window material: Polycarbonate Remote version (wall-mount housing) • Housing material: Polycarbonate • Window material: Polycarbonate Sensor connection housing • Aluminum, AlSi10Mg, coated •...
Page 107
Proline Promag W 800 Cellular radio Technical data Electrodes • Stainless steel, 1.4435 (316L) • Alloy C22, 2.4602 (UNS N06022) Process connections For flanges made of carbon steel: • DN ≤ 300 (12"): with Al/Zn protective coating or protective varnish •...
Technical data Proline Promag W 800 Cellular radio Process connections • EN 1092-1 (DIN 2501) • ASME B16.5 • JIS B2220 • AS 2129 Table E • AS 4087 PN 16 For information on the different materials used in the process connections → 107 Surface roughness Electrodes with 1.4435 (316L);...
Page 109
The device meets the legal requirements of the applicable EU Directives. These are listed in the corresponding EU Declaration of Conformity along with the standards applied. Endress+Hauser confirms successful testing of the device by affixing to it the CE mark. UKCA marking The device meets the legal requirements of the applicable UK regulations (Statutory Instruments).
The application packages can be ordered with the device or subsequently from Endress+Hauser. Detailed information on the order code in question is available from your local Endress+Hauser sales center or on the product page of the Endress+Hauser website: www.endress.com.
For an overview of the scope of the associated Technical Documentation, refer to the following: • W@M Device Viewer (www.endress.com/deviceviewer): Enter the serial number from the nameplate • Endress+Hauser Operations App: Enter the serial number from the nameplate or scan the matrix code on the nameplate Standard documentation Technical Information...
Page 112
Technical data Proline Promag W 800 Cellular radio Supplementary device- Special Documentation dependent documentation Contents Documentation code Heartbeat Technology SD01746D Cellular Module SD02335D Display with Bluetooth Interface SD02655D Using Open Source Software Licenses SD02658D Quick Reference Guide SD02659D OPC-UA SD02663D...