Summary of Contents for Endress+Hauser Proline Promag W 400
Page 1
Detailed information about the device can be found in the Operating Instructions and the other documentation: • On the CD-ROM supplied (not included in the delivery for all device versions). • Available for all device versions via: – Internet: www.endress.com/deviceviewer – Smart phone/tablet: Endress+Hauser Operations App...
Proline Promag W 400 Order code 00X00-XXXX0XX0XXX Ser. No.: X000X000000 TAG No.: XXX000 Serial number www.endress.com/deviceviewer Endress+Hauser Operations App A0023555 Endress+Hauser...
Document information Proline Promag W 400 Document information Symbols used 1.1.1 Safety symbols Symbol Meaning DANGER! DANGER This symbol alerts you to a dangerous situation. Failure to avoid this situation will result in serious or fatal injury. WARNING! This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in WARNING serious or fatal injury.
Proline Promag W 400 Basic safety instructions 1.1.4 Symbols for certain types of information Symbol Meaning Symbol Meaning Permitted Preferred Procedures, processes or actions that Procedures, processes or actions that are permitted. are preferred. Forbidden Procedures, processes or actions that Indicates additional information.
Verification for borderline cases: ‣ For special fluids and fluids for cleaning, Endress+Hauser is glad to provide assistance in verifying the corrosion resistance of fluid-wetted materials, but does not accept any warranty or liability as minute changes in the temperature, concentration or level of contamination in the process can alter the corrosion resistance properties.
If a plastic transmitter housing is permanently exposed to certain steam and air mixtures, this can damage the housing. ‣ If you are unsure, please contact your Endress+Hauser Sales Center for clarification. ‣ If used in an approval-related area, observe the information on the nameplate.
Product description Proline Promag W 400 Product description The device consists of a transmitter and a sensor. Two device versions are available: • Compact version - transmitter and sensor form a mechanical unit. • Remote version - transmitter and sensor are mounted in separate locations.
(depends on device version) and documents present? • If one of the conditions is not satisfied, contact your Endress+Hauser Sales Center. • Depending on the device version, the CD-ROM might not be part of the delivery! The Technical Documentation is available via the Internet or via the Endress+Hauser Operations App.
Storage and transport Proline Promag W 400 Storage and transport Storage conditions Observe the following notes for storage: • Store in original packaging. • Do not remove protective covers or protective caps installed on process connections. • Protect from direct sunlight.
Page 11
Proline Promag W 400 Storage and transport A0015606 5.2.2 Measuring devices with lifting lugs CAUTION Special transportation instructions for devices with lifting lugs ‣ Only use the lifting lugs fitted on the device or flanges to transport the device. ‣...
Installation Proline Promag W 400 Installation Installation conditions 6.1.1 Mounting position Mounting location A0023343 h ≥ 2 × DN Installation in down pipes Install a siphon with a vent valve downstream of the sensor in down pipes whose length h ≥...
Page 13
Proline Promag W 400 Installation Installation in partially filled pipes A partially filled pipe with a gradient necessitates a drain-type configuration. A0017063 Orientation The direction of the arrow on the sensor nameplate helps you to install the sensor according to the flow direction.
Page 14
Installation Proline Promag W 400 Horizontal A0016260 EPD electrode for empty pipe detection Measuring electrodes for signal detection Reference electrode for potential equalization • The measuring electrode plane must be horizontal. This prevents brief insulation of the two measuring electrodes by entrained air bubbles.
Page 15
Proline Promag W 400 Installation If operating outdoors: • Install the measuring device in a shady location. • Avoid direct sunlight, particularly in warm climatic regions. • Avoid direct exposure to weather conditions. Temperature tables Observe the interdependencies between the permitted ambient and fluid temperatures when operating the device in hazardous areas.
Page 16
Installation Proline Promag W 400 Adapters [mbar] 8 m/s 7 m/s 6 m/s 5 m/s 4 m/s max. 8° 3 m/s 2 m/s 1 m/s d / D A0016359 6.1.3 Special mounting instructions Display protection ‣ To ensure that the optional display protection can be easily opened, maintain the following minimum head clearance: 350 mm (13.8 in)
Page 17
Proline Promag W 400 Installation Permanent immersion in water A0017296 4 Engineering unit in m(ft) Replacement of cable gland on connection housing Buried applications A0017298 Endress+Hauser...
Proline Promag W 400 Installation Install the measuring device or turn the transmitter housing so that the cable entries do not point upwards. A0013964 Mounting the seals CAUTION An electrically conductive layer could form on the inside of the measuring tube! Risk of measuring signal short circuit.
Page 20
Installation Proline Promag W 400 Is the device adequately protected from precipitation and direct sunlight? Have the fixing screws been tightened with the correct tightening torque? Endress+Hauser...
Proline Promag W 400 Electrical connection Electrical connection The measuring device does not have an internal circuit breaker. For this reason, assign the measuring device a switch or power-circuit breaker so that the power supply line can be easily disconnected from the mains.
Page 22
Electrical connection Proline Promag W 400 Modbus RS485 The EIA/TIA-485 standard specifies two types of cable (A and B) for the bus line which can be used for every transmission rate. Cable type A is recommended. For detailed information about the specification of the connecting cable, see the Operating Instructions for the device.
Page 23
Proline Promag W 400 Electrical connection 0-20 mA/4-20 mA HART connection version with additional outputs and inputs Signal transmission 0-20 mA/4-20 mA HART with additional outputs and inputs Order code for Terminal numbers "Output" and "Input" Output 1 Output 2...
Page 25
Proline Promag W 400 Electrical connection 7.1.5 Shielding and grounding Modbus The shielding and grounding concept requires compliance with the following: • Electromagnetic compatibility (EMC) • Explosion protection • Personal protection equipment • National installation regulations and guidelines • Observe cable specification → 21.
Page 26
Electrical connection Proline Promag W 400 Where there are large differences in potential between the individual grounding points, only one point of the shielding is connected directly with the reference ground. In systems without potential equalization, therefore, cable shielding of fieldbus systems should only be grounded on one side, for example at the fieldbus supply unit or at safety barriers.
Page 27
Proline Promag W 400 Electrical connection 7.1.6 Requirements for the supply unit Supply voltage Transmitter Order code for "Power supply" Terminal voltage Frequency range AC100 to 240 V 50/ 60 Hz, ±4 Hz Option L AC/DC24 V 50/ 60 Hz, ±4 Hz 7.1.7...
Page 30
Electrical connection Proline Promag W 400 7.2.1 Connecting the remote version WARNING Risk of damaging the electronic components! ‣ Ground the remote version: connect the sensor and transmitter to the same potential equalization. ‣ Only connect the sensor to a transmitter with the same serial number.
Page 31
Proline Promag W 400 Electrical connection 42 41 A0021527 9 Sensor: connection module 7.2.2 Connecting the transmitter WARNING Housing degree of protection may be voided due to insufficient sealing of the housing. ‣ Screw in the screw without using any lubricant. The threads on the cover are coated with a dry lubricant.
Page 32
Electrical connection Proline Promag W 400 Supply voltage connection, 0-20 mA/4-20 mA HART and additional outputs/inputs TX 20 + - + - + - + - 23 20 21 26 27 24 25 10 (0.4) A0017268 ‣ Connect the cable in accordance with the terminal assignment → 22. For supply voltage: open the shock protection cover.
Page 33
Proline Promag W 400 Electrical connection Connecting the supply voltage and PROFIBUS DP PH 2 2627 10 (0.4) A0023164 ‣ Connect the cable in accordance with the terminal assignment → 22. For supply voltage: open the shock protection cover.
Page 34
Electrical connection Proline Promag W 400 Connecting the supply voltage and Modbus RS485 PH 2 2627 10 (0.4) A0024218 ‣ Connect the cable in accordance with the terminal assignment → 22. For supply voltage: open the shock protection cover.
Page 35
Proline Promag W 400 Electrical connection Connecting the supply voltage and EtherNet/IP PH 2 10 (0.4) A0021356 ‣ Connect the cable in accordance with the terminal assignment → 22. For supply voltage: open the shock protection cover. 7.2.3 Ensuring potential equalization...
Electrical connection Proline Promag W 400 Connection examples for standard situations Metal, grounded pipe A0016315 10 Potential equalization via measuring tube Connection example in special situations For detailed information on special cases, see the Operating Instructions for the device.
Page 37
Proline Promag W 400 Electrical connection Addressing mode ex works Software addressing; all DIP switches for hardware addressing are set to OFF. IP address ex works DHCP server active For device addressing via software Setting the address ON OFF Default Ethernet network settings IP 192.168.1.212...
Page 38
Electrical connection Proline Promag W 400 Setting the address ON OFF Not used Write protection A0023061 11 Addressing using DIP switches on the I/O electronics module Disable software addressing (OFF) via the top DIP switch 4 (SW). Set the desired device address via the corresponding DIP switches.
Proline Promag W 400 Electrical connection DIP 3 DIP 1 390 Ω 220 Ω 390 Ω DIP 2 A0023063 12 Termination using DIP switches on the I/O electronics module (for baud rates < 1.5 MBaud) Modbus RS485 To avoid incorrect communication transmission caused by impedance mismatch, terminate the Modbus RS485 cable correctly at the start and end of the bus segment.
Electrical connection Proline Promag W 400 Tighten all housing screws and screw covers. Firmly tighten the cable glands. To ensure that moisture does not enter the cable entry, route the cable so that it loops down before the cable entry ("water trap").
Proline Promag W 400 Operation options Operation options Structure and function of the operating menu 8.1.1 Structure of the operating menu Operating menu for operators and maintenances Language Operation task-oriented Setup Diagnostics Operating menu for experts Expert function-oriented A0014058-EN 14 Schematic structure of the operating menu 8.1.2...
Operation options Proline Promag W 400 Access to the operating menu via the local display X X X X X X 19.184 mA 12.5 X X X X X X Language 20.50 Ã English Deutsch Español Français User ABC_ DEFG...
Page 43
Proline Promag W 400 Operation options 8.2.1 Operational display Status area The following symbols appear in the status area of the operational display at the top right: • Status signals – F: Failure – C: Function check – S: Out of specification –...
Page 44
Operation options Proline Promag W 400 Display area • Icons for menus – : Operation – : Setup – : Diagnostics – : Expert • : Submenus • : Wizards • : Parameters within a wizard • : Parameter locked 8.2.3...
Proline Promag W 400 Operation options 8.2.4 Operating elements Keys and meaning Minus key • In a menu, submenu: Moves the selection bar upwards in a choose list. • With a wizard: Confirms the parameter value and goes to the previous parameter.
Operation options Proline Promag W 400 8.2.5 Further information For further information on the following topics, see the Operating Instructions for the device • Calling up help text • User roles and related access authorization • Disabling write protection via access code •...
Page 47
Proline Promag W 400 Operation options Measuring device Web server Web server must be enabled; factory setting: ON IP address If the IP address of the device is not known: • The IP address can be read out via local operation: "Diagnostics"...
Operation options Proline Promag W 400 Starting the Web browser Enter the IP address of the Web server in the address line of the Web browser: 192.168.1.212 If the IP address of the measuring device is known, enter the defined device address in the address line of the Web browser.
Proline Promag W 400 Operation options 8.3.5 User interface A0017757-EN Picture of device Function row with 6 functions Device tag Header Working area Navigation area Header The following information appears in the header: • Device tag • Device status with status signal •...
System integration Proline Promag W 400 Access to the operating menu via the operating tool For detailed information about access to the operating menu via operating tool, refer to the Operating Instructions for the device . System integration For detailed information on system integration, see the Operating Instructions for the device.
Page 51
Proline Promag W 400 System integration Slot Module Function block 9…10 Discrete Input block 1 to 2 11…12 Discrete Output block 1 to 2 To optimize the data throughput rate of the PROFIBUS network, it is advisable to only configure modules that are processed in the PROFIBUS master system. Any resulting gaps between the configured modules must be assigned to the EMPTY_MODULE.
Page 52
System integration Proline Promag W 400 Factory setting Function block Factory setting: TOTAL Totalizer 1, 2 and 3 Volume flow SETTOT_TOTAL module The module combination consists of the SETTOT and TOTAL functions: • SETTOT: Control the totalizers via the PROFIBUS master.
Page 53
Proline Promag W 400 System integration AO module (Analog Output) Transmit a compensation value from the PROFIBUS master (Class 1) to the measuring device. Assigned compensation values A compensation value is permanently assigned to the individual Analog Output blocks. CHANNEL...
System integration Proline Promag W 400 EMPTY_MODULE module This module is used to assign empty spaces arising from modules not being used in the slots → 50. Cyclic data processing EtherNet/IP 9.2.1 Cyclic data transmission Cyclic data transmission when using the device master file (GSD).
Page 55
Proline Promag W 400 System integration Configuration 3: Exclusive Owner Multicast Input Assembly Configurable Instance Size [byte] Min. RPI (ms) Input Assembly Configurable Configuration 0 x 68 – Output Assembly Fix O → T Configuration 0 x 66 Input Assembly Fix T →...
Page 56
System integration Proline Promag W 400 Configuration 8: Input Only Multicast Input Assembly Configurable Instance Size [byte] Min. RPI (ms) Input Assembly Configurable Configuration 0 x 69 – – Output Assembly Fix O → T Configuration 0 x C7 –...
Page 57
Proline Promag W 400 System integration Possible input values Possible input values 1 to 10: • Off • Temperature • Tube damping fluctuation 0 • Mass flow • Carrier pipe temperature • Tube damping fluctuation 1 • Volume flow • Electronic temperature •...
Page 58
System integration Proline Promag W 400 Designation Description (format) Byte Value 12. Control totalizer 2 (integer) 9…10 0…8 See totalizer 1 13. Not used 11…12 0…8 – 14. Control totalizer 3 (integer) 13…14 0…8 See totalizer 1 15. Not used 15…16...
Proline Promag W 400 Commissioning Commissioning 10.1 Function check Before commissioning the measuring device: ‣ Make sure that the post-installation and post-connection checks have been performed. • "Post-installation check" checklist → 19 • "Post-connection check" checklist → 40 10.2...
Commissioning Proline Promag W 400 10.4 Setting the operating language Factory setting: English or ordered local language X X X X X X X 20.50 Main menu 0104-1 Language English Operation Setup Language 0104-1 English à Deutsch Español Français Language 0104-1 Ã...
Proline Promag W 400 Diagnostic information Wizard/submenu Meaning Output conditioning Define the output conditioning Low flow cut off Set the low flow cut off Empty pipe detection Configure empty pipe detection (EPD) HART input Configure the HART input 10.6 Defining the tag name To enable fast identification of the measuring point within the system, you can enter a unique designation using the Device tag parameter and thus change the factory setting.
Page 62
Diagnostic information Proline Promag W 400 X X X X X X X X X X X X X X 20.50 S801 Supply voltage Menu Diagnostic list Diagnostics 1 S801 Supply voltage Diagnostics 2 Diagnostics 3 Supply voltage (ID:203) S801 0d00h02m25s...