List of Fault Messages (F) and Warning Messages (AL)
Display
Designation
01
Overcurrent
02
Overvoltage
03
Ground fault
08
System fault
09
Undervoltage
13
Undertemperature
14
Overtemperature
15
Motor stalled
16
Motor
overtemperature
17
Motor underload
22
EEPROM checksum
error
25
Watchdog (API)
27
Back EMF
35
Application error
41
IGBT overtemp
Notes
There are subcodes associated with this error. To get the subcode scroll to the M (minute) value within the fault menu. The value listed is the subcode.
Power software V018 IGBT overtemperature. Power software V019 heat sink overtemperature.
Possible Cause
The frequency inverter has detected an excessive
current (> 4 x I N ) in the motor cable
Sudden load increase
Short circuit in motor cable
Inadequate motor
The DC intermediate circuit voltage has exceeded the
internal safety limit
The delay time is too short
High overvoltage peaks in line power
An additional leakage current was detected when
starting by means of a current measurement
Insulation fault in the cables or in the motor
CPU error message
Internal communication fault
The DC intermediate circuit voltage has exceeded
the internal safety limit
Probable cause:
The supply voltage is too low
Internal device fault
Power failure
The IGBT switch temperature is below 14°F (–10°C)
The IGBT switch temperature is above 248°F (120°C)
An excessive temperature warning is issued if the
IGBT switch temperature goes above 230°F (110°C)
The motor blocking protection mechanism has been
triggered
The frequency inverter's motor temperature model
has detected motor overheating. The motor is
overloaded
Motor idle, connection to load machine interrupted
(for example, torn drive belt)
Error when storing parameters
Malfunction
Component fault
Error in microprocessor monitoring
Error in microprocessor monitoring
Malfunction
Component fault
Electromotive force
The voltage induced in the motor with the rotation
is greater than the output voltage of the frequency
inverter
The application is not working
The IGBT switch temperature is above 248°F (120°C)
An excessive temperature warning is issued if the
IGBT switch temperature goes above 230°F (110°C)
M-Max Series Adjustable Frequency Drive MN04020003E—February 2013 www.eaton.com
90
Error and Warning Messages
Instructions
Check the load
Check the motor size
Check the cable
(See parameter P6.6)
Increase braking time
Check the motor cable and the motor
Reset error: Switch input voltage off and on (restart)
If the fault occurs again, contact your local representative
If a brief power failure takes place, reset the fault and restart
the frequency inverter
Check the supply voltage. If it is okay, there is an internal fault
If this is the case, contact your local representative
Check the ambient temperature
Make sure that there is an unobstructed flow of cooling air
Check the ambient temperature
Make sure that the switching frequency is not too high in
relation to the ambient temperature and to the motor load
Check the motor
Decrease the motor load
If the motor is not overloaded, check the temperature model
parameter
This function must be activated at P8.5. The overload
message is set at P8.12 and P8.13
Contact your local Eaton representative
Reset the fault and restart
If the fault occurs again, contact your local representative
The rotation energy is greater than the braking energy
Lengthen deceleration times
Switch on brake chopper and braking resistor
Use higher rated frequency inverters
Contact your local Eaton representative
Make sure that there is an unobstructed flow of cooling air
Check the ambient temperature
Make sure that the switching frequency is not too high in
relation to the ambient temperature and to the motor load