Shielded Cable - Fluke VIBRONET Signalmaster Installation Manual

Table of Contents

Advertisement

62
Cable connections
• Clamp the outer shield between the washers.
• Screw the M20 cable gland and the reduction together.
• Strip the inner cable sheath and connect the inner shield and
signal cable to the respective terminals in the MUX (see 'Coaxial
cable', page 59)

Shielded cable

In electromagnetically contaminated environments use a shielded
cable for connecting the relay outputs.
1. Remove the threaded fitting from the housing and insert the cable
end through it.
2. Strip the insulation from the individual conductors.
3. The cable is inserted through the fitting with outer insulation in-
tact. The exposed length of inner leads should reach to the contact
terminals.
4. Strip an additional 25 mm of outer insulation from the cable.
5. Disassemble the fitting and wrap the exposed portion of the shield
around the sealing sleeve (see below).
6. Reassemble the fitting and refasten it to the housing.
7. Connect the individual leads to the corresponding contacts.
Wrap shield around
sealing sleeve
Lock nut remains
on housing

Advertisement

Table of Contents
loading

Table of Contents