Intrinsically Safe Area: Wiring Diagram For Cabinet - Fluke VIBRONET Signalmaster Installation Manual

Table of Contents

Advertisement

50
Special installations
100 - 240V AC
0,71 - 0,43A
50-60Hz
Digital-
OUT_1
Digital-
OUT_2
Ethernet
CAT 5.E
String1
String2
String3
PE / PA

Intrinsically safe area: Wiring diagram for cabinet

connect to
1X1
L
L1
MS16
N
N
PE
PE
1X2-5V
+
1C1-1
-
1X2-12V
+
1C1-3
-
1T1-
1
1X2-0V
2
1T2-
3
1X2-0V
4
1X2
connect to
Term
1T1+
5V
1P1-4
5V
1T2+
12V
1P1-36
12V
1P1-21
0V
1P1-37
0V
1P1-22
0V
1P1-23
0V
1P1-24
0V
1P1-25
0V
12V-Switch
nc
1K1
connect to
Term
NO1
5
Normally Open (12)
MS12
COM1
6
Common (11)
COM1
7
Common (11)
NC1
8
Normally Close (14)
NO2
9
Normally Open (12)
MS12
COM2
10
Common (11)
COM2
11
Common (11)
NC2
12
Normally Close (14)
connect to
Eth
CAT5 Terminal Box
MS25/4
Tx+
1
Tx-
2
Rx+
3
Rx-
6
Eth. Schield
Shield
50mm Distance to EX
1B1
connect to EX
Triax
MS20 EMV
String1
Shield
String1
Centre
TRIAX-Shield
PA
1B2
connect to EX
Triax
MS20 EMV
String2
Shield
String2
Centre
TRIAX-Shield
PA
1B3
connect to EX
Triax
MS20 EMV
String3
Shield
String3
Centre
TRIAX-Shield
PA
1B1-PA
PE
PE-Cabinet
PE
PE-Cabinet
Earth-Bolt
1X1-PE
2,5mm²
Plate
2,5mm²
Flange Plate
2,5mm²
Cabinet Door
2,5mm²
1X1 wired with (1,5mm²)
PE wired with (2,5mm³)
all other with (0,5mm²), if not
different denoted
Power Supply
connect to
1F1
L1.1
1T1-L
6,3AT
L1.1
1T2-L
N
1T1-N
N
1T2-N
PE
nc
PE
PE-Cabinet
1T1 TBL015-105
L
1X1-L1.1
5,08VDC
N
1X1-N
1T2 TBL015-112
L
1X1-L1.1
12VDC
N
1X1-N
5
PE-Cabinet
1C1
6
nc
VIB-SO-RV
7
nc
C220nF
8
nc
Terminal Strip
Funktion
Term
connect to
5V
nc
5V
nc
12V
1K1-1
12V
nc
0V
1C1-2
0V
1C1-4
0V
1K1-2
0V
nc
0V
nc
0V
nc
12V-Switch
1P1-3
VIB 5.917
Relais
Funktion
Term
connect to
12 Vdc
1
1X2-12V
PG
2
1X2-0V
Sw-In 1
3
1P1-7
Sw-In 2
4
1P1-8
connect to
Tx+
Tx-
1P1-RJ45
RJ45
Rx+
Rx-
PE
VIB 3.550
Limiting Device
Koax
connect to
Shield
1P2-String1
Centre
1P2-String1
PA
PE
VIB 3.550
Limiting Device
Koax
connect to
Shield
1P2-String2
Centre
1P2-String2
PA
PE
VIB 3.550
Limiting Device
Koax
connect to
Shield
1P2-String3
Centre
1P2-String3
PA
PE
PE
1B2-PA
PE
1B3-PA
SIGNALMASTER
1P1
VIB 5.802
connect to
MULTI-IO
Channel
nc
17
A6:Hi (AD1)
nc
33
A6:Lo (AD1)
nc
16
A5:Hi (AD1)
nc
32
A5:Lo (AD1)
nc
15
A4:Hi (AD1)
nc
31
A4:Lo (AD1)
nc
14
A3:Hi (AD3)
nc
30
A3:Lo (AD3)
nc
13
A2:Hi (AD2)
nc
29
A2:Lo (AD2)
nc
12
A1:Hi (AD1)
nc
28
A1:Lo (AD1)
nc
11
OUT5
nc
27
OUT6
nc
44
OUT7
nc
20
OUT8
nc
9
P1
nc
42
P2
1K1-3
7
OUT1
1K1-4
8
OUT2
nc
40
OUT3
nc
41
OUT4
nc
5
IN1
nc
6
IN2
nc
38
IN3
nc
39
IN4
nc
10
KP/AC
nc
43
SYNC
1X2-12V-Switch
3
12V Switch
1X2-12V
36
12 V Supply
1X2-5V
4
5 V Supply
nc
34
PE
nc
35
KP/DC
nc
49, 50
AG
nc
47,48
AG
nc
45,46
AG
nc
26
PG
1X2-0V
24,25
PG
1X2-0V
22,23
PG
1X2-0V
21, 37
PG
nc
1
LAN: TX+
nc
2
LAN: TX-
nc
18
LAN: RX+
nc
19
LAN: RX-
nc
D-SUB RS232/1
nc
D-SUB RS232/2
Eth-RJ45
RJ45
Eth 100MBit
1P2-SYSTEM-BUS
D-SUB SYSTEM-BUS
nc
D-SUB EVENT-BUS
1P2
VIB 5.815-3
connect to
Term
Channel
1B1-VIB 3.550
TNC
String 1
1B2-VIB 3.550
TNC
String 2
1B3-VIB 3.550
TNC
String 3
nc
BNC
100mV/g
1P1-SYSTEM-BUS
D-SUB
SYSTEM-BUS
nc
D-SUB
SPM-BUS
AC Connection
1,5mm²
Fuse 6,3A
VIBRONET Signalmaster cabinet
Customer:
PRUFTECHNIK CM, (DE) 88250
Weingarten
Project:
VIB 5.890-3 SIGNALMASTER
Standard Package SAP
16.09.2015
Date:
V3
50-pol
RD
BK
RD
BK
RD
BK
RD
BK
RD
BK
RD
BK
YE
YE
YE
YE
YE
YE
YE
YE
YE
YE
YE
YE
YE
YE
YE
YE
RD
RD
RD
GN/YE
YE
DBU
DBU
DBU
DBU
DBU
DBU
DBU
BN
RD
OG
BU
9-pol
9-pol
15-pol
15-pol
SP-Modul
Signal

Advertisement

Table of Contents
loading

Table of Contents