Chapter 8:
Cable connections

Electrical cable

The connections of the relay outputs and the supply lines are made
using commercial single or multicore electrical cables (Wire size:
AWG 24-12). For the terminals of the relay module 1K1 you need
matching cable end sleeves.
• Strip the cable by 8 mm.
• Open the screw above the respective connection and insert the
lead.
• Tighten up the screw again.
8 mm
Electrical cable,
Wire size: AWG 24-12

Coaxial cable

Coaxial cables are used to connect the sensors to the MUXes. Proceed
as follows:
• Use an appropriate tool (e.g. cable stripper VIB 81052 ) to strip the
free cable end. Please refer to the below diagram for details.
• Carefully wrap the exposed portion of the shield back around the
cable sheath.
• Connect the cable to the respective terminal on the MUX board.
10 mm 7 mm
RG 58 coaxial cable
To open / close the terminal
Cable stripper VIB 81052
59
Cable connections