Lennox iComfort M30 Installation And Setup Manual page 25

Smart thermostat
Hide thumbs Also See for iComfort M30:
Table of Contents

Advertisement

Parameter Name
Stage 2 HP Lock Temp
Feels Like
Wider Set Point Range
Heating Mode: Normal
or Comfort
Smart Away
Low Balance Point
High Balance Point
Deadband
Table 6. Parameter Descriptions
Definition
The User shall be able to select the STG 2 HP lock temp from 40F, 45F, 50F, 55F or OFF. The value is used
in dual fuel algorithm to lock the second stage of compressor .The default is OFF which means it is disabled
and is not used in dual fuel algorithm. If system has only 1st stage equipment, this item is hidden from installer
screen. For more information see "Stage 2 HP Lock Temp" on page 28.
This feature will display the home temperature based on a combination of inputs. Feels Like uses outdoor
temperature, indoor temperature, and indoor humidity to determine the "feels like" condition of the home.
By default your thermostat operates within a range of 60-90°F. Enabling this options changes the range to
44-99°F.
Options are Normal and Comfort. Default is Normal. When changing to Comfort Mode, several parameters
are automatically modified for optimal system operations. The changed parameters are listed on the screen
when set to Comfort.
• Normal - This setting cools the home to the desired temperature setting. Once second-stage is activated
by timer or differential, it will not stage down to first-stage until the next heating cycle demand.
• Comfort - This is when the system could automatically stage up or down based on the current load
demand.
This setting when enabled controls the temperature in the home when no one is home. For this to function, the
Lennox Mobile app needs to be installed on a mobile device.
(Multistage Heat Pump Model only) -The default is 25°F. This option will only be available if an outdoor sensor
is installed. If the outside temperature is below the programmed Low Balance Point, then the compressor stage
operation is disallowed. This protects the compressor from operation and damage in cold outdoor tempera-
tures. Also, if the heat pump is not effective at a low outdoor temperature, then it is more comfortable and effi-
cient to go directly to the second stage. Low Balance Point can be disable in this screen. When this is enable,
the options are from –40°F to (the High Balance Point temperature -2) in 1.0°F steps.
The default is 50°F. This option is only available if an outdoor sensor is installed. If the outside temperature is
above the High Balance point, then the auxiliary heat stage is disallowed. This prevents the more expensive
auxiliary heat stage from operating, and forces the more efficient heat pump to satisfy the demand. High
Balance Point can be disable in this screen. When this is enable, the high balance point range is from (the low
balance point + 2) up to 75°F.
The deadband setting is the minimum difference between the cooling and heating setpoints. This setting is
used in auto-changeover to ensure smooth equipment operation. It also allows for flexibility of Humiditrol oper-
ation. The default deadband is 3 and the deadband is adjustable from 3 to 9°F degrees.