Lennox iComfort M30 Installation And Setup Manual page 18

Smart thermostat
Hide thumbs Also See for iComfort M30:
Table of Contents

Advertisement

MENU
SMOOTH SETBACK RECOVERY
OFFSET
STAGE DIFFERENTIAL
STAGE DELAY
H/C STAGES LOCKED IN
Table 5. Advanced Settings
SETTING (default is bold)
Enabled or Disabled
Temperature Offset - 0°F
Humidity Offset - 0%
Stage 1 - 1.0°F
Stage 2 - 1.0°F
Stage 3 - 0.5°F
Stage 4 - 0.5°F
On or Off
Stage 2 through 4 - 20 min.
Enable or Disable
18
Notes:
When enabled, smooth set back begins
recovery up to two hours before the
programmed time so that the programmed
temperature is reached at the corresponding
programmed event time. Assume 12°F
(6.72°C) per hour for first-stage gas/electric
heating and 6°F (3.36°C) per hour for first-
stage compressor based heating or cooling.
With Smooth Set Back disabled, the system
will start a recovery at the programmed time.
Options are enabled or disabled. Default is
enabled.
Adjustable (-5 to 5°F)
Adjustable (-10 to 10%)
Adjustable (0.5 to 8.0°F)
Adjustable (0.5 to 8.0°F)
Adjustable (0.5 to 8.0°F)
Adjustable (0.5 to 8.0°F)
Adjustable (5 to 120 minutes). Default is 20
min.
Turns heating stages off separately