Is the correct spare part for the indoor
unit PCB installed?
No
Prerequisite: First perform all earlier checks of the indoor unit PCB, see
"2.6.1 Checking
procedures" [
Prerequisite: Stop the unit operation via the user interface.
Prerequisite: Turn OFF the respective circuit breaker.
1 Check that all wires are properly connected and that all connectors are fully
plugged‑in.
2 Check that no connectors or wires are damaged.
3 Check that the wiring corresponds with the wiring diagram, see
4
diagram" [
 137].
INFORMATION
Correct the wiring as needed.
Is the problem solved?
Yes
No
Prerequisite: First perform all earlier checks of the indoor unit PCB, see
"2.6.1 Checking
procedures" [
1 Measure the continuity of the fuse. If no continuity is measured, the fuse has
blown.
a
a
Fuse
Blown fuse on the indoor unit PCB?
Yes
Action
Replace the indoor unit PCB, see
"2.6.2 Repair
4
 68].
Action
No further actions required.
Return to
procedures" [
PCB and continue with the next
procedure.
4
 68].
Action
Replace the blown fuse, see
"2.6.2 Repair
ATXP20~35 + FTXP20~71 + ARXP20~35 + RXP20~71
4
procedures" [
 71].
"5.2  Wiring
"2.6.1 Checking
4
 68] of the indoor unit
4
procedures" [
 71].