Daikin Split Comfora R32 Service Manual page 128

Hide thumbs Also See for Split Comfora R32:
Table of Contents

Advertisement

3
|
Third party components
To replace the clogged/leaking part of the refrigerant circuit
To recuperate the refrigerant
Service manual
128
Is the problem solved?
Yes
No
1 See the correct procedure for the component that needs to be repaired. See
also
"Repair
information" [
Is the problem solved?
Yes
No
Prerequisite: Stop the unit operation via the user interface.
1 Manually open all expansion valves.
2 Connect the vacuum pump, manifold, recovery unit, and refrigerant bottle to
the service port of the refrigerant circuit as shown below.
L
a
a
Vacuum pump
b
Connect flexible hose to service port
c
To recovery pump
L
Low pressure
H
High pressure
V
Vacuum
R
Refrigerant
3 To add refrigerant, see
Is the problem solved?
Yes
Action
No further actions required.
Return to the troubleshooting of the
specific error and continue with the
next procedure.
4
 129] for more details.
Action
No further actions required.
Return to the troubleshooting of the
specific error and continue with the
next procedure.
H
V
R
b
"3.2.2 Repair
procedures" [
Action
No further actions required.
c
4
 127].
ATXP20~35 + FTXP20~71 + ARXP20~35 + RXP20~71
Split Comfora R32
ESIE18-01C – 2020.07

Advertisement