To perform an electrical check of the compressor
Service manual
46
INFORMATION
The compressor dampers may look different.
Compressor dampers are in a good
condition?
Yes
No
1 First perform a mechanical check of the compressor, see
4
procedures" [
 44].
DANGER: RISK OF ELECTROCUTION
Wait for at least 10 minutes after the circuit breaker has been turned OFF, to be sure
the rectifier voltage is below 10 V DC before proceeding.
2 Remove the cover of the compressor wire terminals.
a
Compressor wire terminals cover
3 Disconnect the Faston connectors from the compressor wire terminals U, V
and W.
INFORMATION
Note the position of the Faston connectors on the compressor wire terminals to
allow correct connection during installation.
Action
Perform an electrical check of the
compressor, see
4
procedures" [
 44].
Replace the compressor, see
"2.2.2 Repair
procedures" [
a
ATXP20~35 + FTXP20~71 + ARXP20~35 + RXP20~71
"2.2.1 Checking
4
 50].
"2.2.1  Checking
Split Comfora R32
ESIE18-01C – 2020.07