Operating Instructions
Micropilot M FMR244
Level-Radar
8
BA249F/00/en/05.08
71073069
Valid as of software version:
01.05.00

Advertisement

Table of Contents
loading

Summary of Contents for Endress+Hauser PROFIBUS Micropilot M FMR244

  • Page 1 Operating Instructions Micropilot M FMR244 Level-Radar BA249F/00/en/05.08 71073069 Valid as of software version: 01.05.00...
  • Page 2 An overview of all device functions can be found on Page 104. The operating manual BA291F/00/en "Description of the instrument functions for Micropilot M" provides an extensive description of all device functions, which can be found on the enclosed CD-ROM. Endress+Hauser...
  • Page 3: Table Of Contents

    Operational safety ......4 9.10 Contact addresses of Endress+Hauser ... 98 Notes on safety conventions and symbols .
  • Page 4: Safety Instructions

    (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. " Caution! Changes or modifications not expressly approved by the part responsible for compliance could void the user’s authority to operate the equipment. Endress+Hauser...
  • Page 5: Notes On Safety Conventions And Symbols

    A connection made to the plant grounding system which may be of type e.g. neutral star or equipotential line according to national or company practice Temperature resistance of the connection cables t >85°C States, that the connection cables must be resistant to a temperature of at least 85 °C. Endress+Hauser...
  • Page 6: Identification

    NEPSI Ex ia IIC T6 NEPSI Ex d (ia) IIC T6 R NEPSI Ex nAL IIC T6 Special version, to be specified Antenna: 40mm/1-1/2", PTFE encapsulated 80mm/3", PP cladded Special version, to be specified FMR244- Product designation (part 1) Endress+Hauser...
  • Page 7 Thread G1/2 Thread NPT1/2 Plug M12 Plug 7/8" Special version, to be specified Additional option: A Basic version Advanced dynamics (max MB=70m) (SIL on request) MB=measuring range GL/ABS/NK marine certificate Special version, to be specified FMR244- Complete product designation Endress+Hauser...
  • Page 8: Scope Of Delivery

    The device complies with the applicable standards and regulations as listed in the EC declaration of conformity and thus complies with the statutory requirements of the EC directives. Endress+Hauser confirms the successful testing of the device by affixing to it the CE mark.
  • Page 9: Mounting

    Mark on process connector pointed towards the slots or vent holes! mark at threaded boss Allen key G 1½” 4 mm / 0.1" max. torque 0.5 Nm 1½ NPT F12 or T12 housing Caution! Tighten instrument only at the threaded boss. AF 60 max. torque 20 Nm L00-FMR244xx-17-00-00-en-001 Endress+Hauser...
  • Page 10: Incoming Acceptance, Transport, Storage

    Do not lift the measuring instrument by its housing in order to transport it. 3.2.3 Storage Pack the measuring instrument so that is protected against impacts for storage and transport. The original packing material provides the optimum protection for this. The permissible storage temperature is -40 °C…+80 °C. Endress+Hauser...
  • Page 11: Installation Conditions

    Micropilot M FMR244 with PROFIBUS PA Mounting Installation conditions 3.3.1 Dimensions Housing dimensions max. 110 ENDRESS+HAUSER F12 housing (Aluminium) L00-F12xxxx-06-00-00-en-001 max. 100 ENDRESS+HAUSER T12 housing (Aluminium) L00-T12xxxx-06-00-00-en-001 Endress+Hauser...
  • Page 12 Micropilot M FMR 244 - process connection, old type of antenna F12 / T12 housing Group 20 / Code 2 Threaded connection G 1 ½” or 1 ½ NPT Ø 71.5 PVDF PTFE (FDA-listed TFM 1600) Ø 39 L00-FMR244xx-06-00-00-en-005 Endress+Hauser...
  • Page 13 • Stilling well: a stilling well can always be used to avoid interference. • Metallic screens (3) mounted at a slope spread the radar signals and can, therefore, reduce interference echoes. Please contact Endress+Hauser for further infor- mation. L00-FMR2xxxx-17-00-00-xx-009 Endress+Hauser...
  • Page 14 >85°C user user ENDRESS MICROPIL +HAUSER Endre Endre ss+Ha ss+Ha Order Code: OT II Ser.-No.: Messbereich Measuring range U 16...36 max. 20 IP 65 4...20 mA V DC T >70°C t >85°C L00-FMR2xxxx-17-00-00-xx-013 Please contact Endress+Hauser for further information. Endress+Hauser...
  • Page 15 5.25 m (17.15 ft) ⎯ 35 m (114 ft) 6.12 m (19.95 ft) ⎯ 40 m (131 ft) 7.00 m (22.92 ft) ⎯ 45 m (147 ft) 7.87 m (25.72 ft) ⎯ 60 m (196 ft) 10.50 m (34.30 ft) Endress+Hauser...
  • Page 16 • The tank diameter should be greater than D (see Fig.), the tank height at least H (see Fig.). A [mm (inch)] B [m (inch)] C [mm (inch)] D [m (inch)] H [m (inch)] FMR244 150 (6) > 0,2 (> 8) 50...250 (2...10) > 0,2 (> 8) > 0,3 (> 12) Endress+Hauser...
  • Page 17 … 4...10 e.g. concentrated acids, organic solvents, esters, aniline, alcohol, acetone, … > 10 conducting liquids, e.g. aqueous solutions, dilute acids and alkalis Treat Ammonia NH as a medium of group A, i.e. use FMR230 in a stilling well. Endress+Hauser...
  • Page 18 Measuring range [m (ft)] FMR244: 40 mm (1½") 80 mm (3") Buffer tank (6.6) (13) (16) (16) (16) (24) (32) (32) (32) (49) (49) (82) Moving surfaces (e.g. continuous filling, from above, mixing jets). Measuring range [m (ft)] Endress+Hauser...
  • Page 19 Process tank with agitator (3.2) (6.6) (8.2) (9.8) (16) (16) (26) (39) (49) Turbulent surface. Single stage agitator <60 RPM. Measuring range [m (ft)] FMR244: 40 mm (1½") Stilling well A, B, C, D (65) Measuring range [m (ft)] Endress+Hauser...
  • Page 20: Installation Instructions

    500 mm can be accepted if this should not be possible due to mechanical Ø D reasons. Note! Please contact Endress+Hauser for application with higher nozzle. • The antenna must be aligned vertically. L00-FMR244xx-17-00-00-de-002 Antenna size 40 mm (1½") D [mm (inch)] 39 (1.5)
  • Page 21 • After mounting (flange), the housing can be turned 350° in order to simplify access to the display and the terminal compartment. Ø D L00-FMR244xx-17-00-00-xx-011 Antenna size 80 mm (3") D [mm (inch)] 80 (3) 100 (4) 150 (6) H [mm (inch)] < 500 (< 20) < 500 (< 20) < 500 (< 20) Endress+Hauser...
  • Page 22 Micropilot M FMR244 with PROFIBUS PA Mounting bracket Dimensions: 4 x Ø 5.5 Ø 9 L00-FMR244xx-06-00-00-xx-008 Note! T12 housing mounting limited only. Antenna size 1½" / 40 mm D [mm/inch] 39 / 1.5 H [mm/inch] < 85 / < 3.4 Endress+Hauser...
  • Page 23 • Do not weld through the pipe wall. The inside of the stilling well must remain smooth. In case of unintentional welding through the pipe, the weld seam and any unevenness on the inside need to be carefully removed and smoothened. Otherwise, strong interference echoes will be generated and material build-up will be promoted. Endress+Hauser...
  • Page 24 < 1/10 Ø pipe 100 % < 1/10 Ø pipe full bore ball valve inside of holes deburred Diameter of o pening of ball valve must always be equivalent to pipe diameter. Avoid edges and constrictions. L00-FMR244xx-17-00-00-en-005 Endress+Hauser...
  • Page 25: Post-Installation Check

    • Have the flange screws been tightened up with the respective tightening torque? • Are the measuring point number and labeling correct (visual check)? • Is the measuring instrument adequately protected against rain and direct sunlight (→ Page 79)? Endress+Hauser...
  • Page 26: Wiring

    Micropilot M FMR244 with PROFIBUS PA Wiring Quick wiring guide Wiring in F12 housing " Before connection please note the following: ENDRESS+HAUSER ● PROFIBUS devices are marked on the nameplate (1). The MICROPILOT M IP65 voltage is determined by the PROFIBUS standard and the...
  • Page 27 Micropilot M FMR244 with PROFIBUS PA Wiring Wiring in T12 housing " Before connection please note the following: ENDRESS+HAUSER ● MICROPILOT M PROFIBUS devices are marked on the nameplate (1). The IP65 voltage is determined by the PROFIBUS standard and the...
  • Page 28 Micropilot M FMR244 with PROFIBUS PA Wiring with M12 connector Before connection please note the following: " ENDRESS+HAUSER ● PROFIBUS devices are marked on the nameplate (1). The MICROPILOT M voltage is determined by the PROFIBUS PA standard and the...
  • Page 29: Connecting The Measuring Unit

    Connection with M12 plug The Micropilot M PROFIBUS PA sensor version with M12 plug is supplied ready wired and need only be connected to the bus by means of a suitable cord set. Endress+Hauser...
  • Page 30: Recommanded Connection

    • Is the cable gland tight? • Is the M12 connector screwed tight? • Is the housing cover screwed tight? • If auxiliary power is available: Is the instrument ready for operation and does the liquid crystal display show any value? Endress+Hauser...
  • Page 31: Operation

    (e.g. "medium property (003)") Ü 5) Press ) once return to previous function (e.g. "tank shape (002)") Ü Press ) twice return to Group selection 6) Press ) to return to Measured value display L00-FMR250xx-19-00-00-en-002 Endress+Hauser...
  • Page 32 The third digit numbers the individual functions within the function group: → • tank shape • basic setup • medium property • process cond..Hereafter the position is always given in brackets (e.g. "tank shape" (002)) after the described function. Endress+Hauser...
  • Page 33: Display And Operating Elements

    The VU331 LCD display can be removed to ease operation by simply pressing the snap-fit (see graphic above). It is connected to the device by means of a 500 mm cable. Note! To access the display the cover of the electronic compartment may be removed even in hazardous area (IS and XP). Endress+Hauser...
  • Page 34 This alarm symbol appears when the instrument is in an alarm state. If the symbol flashes, this indicates a warning. LOCK_SYMBOL This lock symbol appears when the instrument is locked,i.e. if no input is possible. COM_SYMBOL This communication symbol appears when a data transmission via e.g. HART, PROFIBUS PA or FOUNDATION Fieldbus is in progress. Endress+Hauser...
  • Page 35 Contrast settings of the LCD Hardware lock / unlock After a hardware lock, an operation of the instrument via display or communication is not possible! The hardware can only be unlocked via the display. An unlock parameter must be entered to do so. Endress+Hauser...
  • Page 36: Local Operation

    It is not possible to unlock the hardware by communication. All parameters can de displayed even if the instrument is locked. ⇒ ENDRESS + HAUSER press simultaneous – ⇓ ⇓ The LOCK_SYMBOL appears on the LCD. Endress+Hauser...
  • Page 37 There is no need to change these parameters under normal circumstances and consequently, they are protected by a special code known only to the E+H service organization. Please contact Endress+Hauser if you have any questions.
  • Page 38 The tank map can also be reset in the "mapping" (055) function of the "extended calibr." (05) function group. This reset is recommended whenever an instrument with an unknown 'history' is to be used in an application or if a faulty mapping was started: • The tank map is deleted. The mapping must be recommenced. Endress+Hauser...
  • Page 39: Display And Acknowledging Error Messages

    • The "diagnostics" (0A) function group can display current errors as well as the last errors that occurred. • If several current errors occur, use to page through the error messages. • The last occurring error can be deleted in the "diagnostics" (0A) function group with the funktion"clear last error" (0A2). Endress+Hauser...
  • Page 40: Profibus Pa Communication

    EEx ia IIC according to the FISCO model). The bus power is supplied by the segment coupler. On- site- as well as remote operation are possible. For detailed information on the PROFIBUS-PA standard refer to Operation Instructions BA 198F/00/en and the standards EN 50 170/DIN 19 245 (PROFIBUS-PA) and EN 50 020 (FISCO model). Endress+Hauser...
  • Page 41 DIP-switches 1 to 7 according to the following table: Switch No. Value in position "OFF" Value in Position "ON" The new address becomes valid 10 seconds after switching. It results a new device restart. Endress+Hauser...
  • Page 42 PA139700.gsd for devices with one analogue input block. This file supports the transmission of the main value. Transmission of a second cyclic value or a display value is not supported. When the universal database is used, the option "profile" must be selected in the function "Ident number" (061). Endress+Hauser...
  • Page 43 This is a value which can be transferred from the PLC to the Micropilot M in order to be shown on the display. FREE PLACE This module must be applied during configuration (see below), if the 2nd cyclic value or the display value are not to appear in the data telegram. Endress+Hauser...
  • Page 44 Die Output-Daten von der SPS für das Display am Gerät haben folgende Struktur: Index Data Access Format/Remarks Input Data 0, 1, 2, 3 Display value write 32 bit floating point number (IEEE-754) Status code for Display value write see "Status codes" Endress+Hauser...
  • Page 45 40 F0 00 00 (hex) = 0100 0000 1111 0000 0000 0000 0000 0000 (bin) (129-127) = (-1) x (1 + 2 = 1 x 2 x (1 + 0.5 + 0.25 + 0.125) = 1 x 4 x 1.875 = 7.5 Endress+Hauser...
  • Page 46 89 Hex GOOD LOW_LIM (alarm active) 8A Hex GOOD HI_LIM (alarm active) 8D Hex GOOD LOW_LOW_LIM (alarm active) 8E Hex GOOD HI_HI_LIM (alarm active) If a status other than "GOOD" is sent to the device, the display indicates an error. Endress+Hauser...
  • Page 47 If the application program is badly designed, however, this limit can be reached quickly, and the RAM will fail The device Micropilot M supports MS2AC communication with two SAPs. The device Micropilot M does not support MS1AC communication. Endress+Hauser...
  • Page 48 PV Scale V0H5 Array of FLOAT static V0H6 Out Scale DS-36* static Linearisation type UNSIGNED8 static Channel UNSIGNED16 static PV fail safe time FLOAT non-vol. Fail safe type UNSIGNED8 static Fail safe value FLOAT static Alarm Hysteresis FLOAT static Endress+Hauser...
  • Page 49 Block parameters Software revision OSTRING constant Hardware revision OSTRING constant Device manufacturer ID UNSIGNED16 constant Device ID OSTRING constant Device serial number OSTRING constant Diagnosis OSTRING dynamic Diagnosis extension OSTRING dynamic Diagnosis mask OSTRING constant Diagnosis mask ext. OSTRING constant Endress+Hauser...
  • Page 50 Device SW No. V9H3 UNSIGNED16 dynamic set unit to bus V6H1 UNSIGNED8 static input value V6H6 FLOAT+U8+U dynamic Select Main value V6H5 UNSIGNED8 dynamic PA profile revision V6H7 OSTRING constant 114- Gap reserved 119- Phys. Block View 1 OSTRING dynamic 127- Endress+Hauser...
  • Page 51 V3H1 UNSIGNED8 static customer unit V3H2 UNSIGNED16 static table no. V3H3 UNSIGNED8 static input volume V3H5 FLOAT static max. scale V3H6 FLOAT static diameter vessel V3H7 FLOAT static check distance V4H1 UNSIGNED8 static range of mapping V4H2 FLOAT static Endress+Hauser...
  • Page 52 V9H5 FLOAT dynamic measured level V9H6 FLOAT dynamic application par. V9H8 UNSIGNED8 dynamic tag no. VAH0 STRING const profile version VAH1 STRING static protocol+sw-no. VAH2 STRING const serial no. VAH4 STRING static distance unit VAH5 UNSIGNED16 static Endress+Hauser...
  • Page 53 • FOUNDATION Fieldbus, PROFIBUS PA and HART via the FXA193/FXA291 service interface Note! You can use the ToF Tool to configure the Endress+Hauser parameters for devices with "FOUNDATION Fieldbus signal". You need an FF configuration program to be able to configure all the FF-specific parameters and to integrate the device into an FF network.
  • Page 54 • HART via Commubox FXA191 and the RS 232 C serial interface of a computer • HART via Commubox FXA195 and the USB port on a computer • PROFIBUS PA via segment coupler and PROFIBUS interface card Menu-guided commissioning MicropilotM-en-305 Signal analysis via envelope curve MicropilotM-en-306 Endress+Hauser...
  • Page 55 Micropilot M FMR244 with PROFIBUS PA Operation Tank linearisation MicropilotM-en-307 Endress+Hauser...
  • Page 56: Commissioning

    Select the basic unit (this message appears the first time the instrument is switched on) ⇓ The current measured value is displayed ⇓ After is pressed, you reach the group selection. This selection enables you to perform the basic setup Endress+Hauser...
  • Page 57: Basic Setup

    E = empty calibr. (= zero), setting in 005 F = full calibr. (= span), setting in 006 D = distance (distance flange / product), display in 0A5 L = level, display in 0A6 SD = safety distance, setting in 015 L00-FMR244xx-19-00-00-en-001 Endress+Hauser...
  • Page 58 All functions are described in detail, as is the overview of the operating menu itself, in the manual “Description of the instrument functions − BA291F”, which is found on the enclosed CD- ROM. Note! The default values of the parameters are typed in boldface. Endress+Hauser...
  • Page 59: Basic Setup With The Vu 331

    • empty calibr. • full calibr. • full calibr. • pipe diameter • check distance • check distance • range of mapping • range of mapping • start mapping • start mapping • . . . • . . . Endress+Hauser...
  • Page 60 Micropilot M FMR244 with PROFIBUS PA Function "tank shape" (002), liquids only ⇒ ENDRESS + HAUSER – This function is used to select the tank shape. Selection: • dome ceiling • horizontal cyl • bypass • stilling well • flat ceiling • sphere L00-FMR2xxxx-14-00-06-en-007 Endress+Hauser...
  • Page 61 … 4...10 e.g. concentrated acids, organic solvents, esters, aniline, alcohol, acetone, … >10 conducting liquids, e.g. aqueous solutions, dilute acids and alkalis Treat Ammonia NH3 as a medium of group A, i.e. use FMR 230 in a stilling well. Endress+Hauser...
  • Page 62 The output damping is set to 0. → smoothed meas. value → rapid reaction time → medium fast reaction time → possibly unsteady meas. value → minimization of effects by agitator blades Endress+Hauser...
  • Page 63 – Grain, seeds 2.5...4 – Ground stones – Sand – Naturally moist (ground) stones, ores 4...7 – Salt – Metallic powder > 7 – Carbon black – Coal The respective lower group applies for very loose or loosened bulk solids. Endress+Hauser...
  • Page 64 Commissioning Micropilot M FMR244 with PROFIBUS PA Function "process cond." (00C), solids only ⇒ ENDRESS + HAUSER – This function is used to select the process conditions. Selection: • standard • fast change • slow change • test:no filter Endress+Hauser...
  • Page 65 This function is used to enter the distance from the flange (reference point of the measurement) to the minimum level (=zero). L00-FMR2xxxx-14-00-06-en-008 " Caution! For dish bottoms or conical outlets, the zero point should be no lower than the point at which the radar beam hits the bottom of the tank. Endress+Hauser...
  • Page 66 If bypass or stilling well was selected in the "tank shape" (002) function, the pipe diameter is requested in the following step. Note! For FMR 244, the end of measuring range should not be chosen closer than 150 mm/ 6 inch to the tip of the antenna, especially if there is development of condensate. Endress+Hauser...
  • Page 67 Microwaves propagate more slowly in pipes than in free space. This effect depends on the inside diameter of the pipe and is automatically taken into account by the Micropilot. It is only necessary to enter the pipe diameter for applications in a bypass or stilling well. Endress+Hauser...
  • Page 68 • At the moment, an interference is being evaluated • Therefore, a mapping is carried out including the presently measured echoes • The range to be suppressed is suggested in the "range of mapping" (052) function Endress+Hauser...
  • Page 69 • off → no mapping is carried out • on → mapping is started During the mapping process the message "record mapping" is displayed. " Caution! A mapping will be recorded only, if the device is not in alarm-state. Endress+Hauser...
  • Page 70 • Distance correct − level incorrect → Check "empty calibr." (005) • Distance incorrect − level incorrect → continue with the next function, "check distance" (051) ⇒ ENDRESS + HAUSER – ⇓ After 3 s, the following message appears Endress+Hauser...
  • Page 71 Note! An orientation of the Micropilot can help to optimise measurement in applications with very weak level echos or strong interference echos by increasing the useful echo/reducing the interference echo (see "Orientation of the Micropilot" on Page 90). Endress+Hauser...
  • Page 72 Horizontal Zoom mode Firstly, go into the envelope curve display. Then press to switch to the envelope curve navigation. You are then in Horizontal Zoom mode. Either is displayed. • increases the horizontal scale. • reduces the horizontal scale. L00-FMxxxxxx-07-00-00-yy-007 Endress+Hauser...
  • Page 73 The set increases and shifts are retained. Only when you reactivate the "recording curve" (0E2) function does the Micropilot use the standard display again. ⇒ ENDRESS + HAUSER – ⇓ After 3 s, the following message appears Endress+Hauser...
  • Page 74: Basic Setup With The Endress+Hauser Operating Program

    Commissioning Micropilot M FMR244 with PROFIBUS PA Basic Setup with the Endress+Hauser operating program To carry out the basic setup with the operating program, proceed as follows: • Start the operating program and establish a connection. • Select the "basic setup" function group in the navigation window.
  • Page 75 – tank shape – medium property – process cond. MicropilotM-en-302 Basic Setup step 3/4: If "dome ceiling", "horizontal cyl", "..." is selected in the "tank shape" function, the following display appears on the screen: • empty calibr. • full calibr. MicropilotM-en-303 Endress+Hauser...
  • Page 76 After the basic setup, an evaluation of the measurement using the envelope curve is recommended. MicropilotM-en-306 Note! If the level of echo is very weak or there is a heavy interference echo, an orientation of the Micropilot can help optimise the measurement (increase of the useful echo/reduction of the interference echo). Endress+Hauser...
  • Page 77 Micropilot M FMR244 with PROFIBUS PA Commissioning 6.5.2 User-specific applications (operation) For details of setting the parameters of user-specific applications, see separate documentation BA291F/00/en "Description of the instrument functions for Micropilot M" on the enclosed CD- ROM. Endress+Hauser...
  • Page 78: Maintenance

    They contain the related replacement instructions. All the spare parts kits which you can order from Endress+Hauser for repairs to the Micropilot M are listed with their order numbers on Page 92 ff.. Please contact Endress+Hauser Service for further information on service and spare parts.
  • Page 79: Accessories

    Micropilot M FMR244 with PROFIBUS PA Accessories Accessories Various accessories, which can be ordered separately from Endress+Hauser, are available for the Micropilot M. Weather protection cover A Weather protection cover made of stainless steel is recommended for outdoor mounting (order code: 543199-0001).
  • Page 80 JIS 10K 80A JIS 10K 100A JIS 10K 150A Material EPDM Process pressure -0.1 bar ... 0.1 bar (-1.45 psi ... 1.45 psi) Process temperature -40 °C ... +80 °C (-40 °F ... +176 °F) Order code 71068375 71068376 71068377 Endress+Hauser...
  • Page 81 Accessories Commubox FXA291 The Commubox FXA291 connects Endress+Hauser field instruments with CDI interface (= Endress+Hauser Common Data Interface) to the USB interface of a personal computer or a notebook. For details refer to TI405C/07/en. Note! For the following Endress+Hauser instruments you need the "ToF Adapter FXA291" as an additional accessory: •...
  • Page 82 20m/65ft; for HART 20m/65ft; for PROFIBUS PA/FOUNDATION Fieldbus Additional option: Basic version Mounting bracket, pipe 1"/ 2" FHX40 - Complete product designation For connection of the remote display FHX40 use the cable which fits the communication version of the respective instrument. Endress+Hauser...
  • Page 83: Trouble-Shooting

    Correct configuration Communication ok? Ready does not function of COM port on PC Contact E+H Service Instrument Not ok measures Check basic setup Repeat Measurement ok? Ready incorrectly basic setup Proceed according to section 'Trouble shooting’ in OM L00-FMR2xxxx-19-00-00-en-010 Endress+Hauser...
  • Page 84: System Error Messages

    W611 less than 2 linearisation number of entered linearisation points < 2 correct linearisation table points for channel 1 W621 simulation ch. 1 on simulation mode is active switch off simulation mode Endress+Hauser...
  • Page 85 E671 linearisation ch1 not linearisation table is in edit mode activate linearisation table complete, not usable W681 current ch1 out of range current out of range (3.8 mA...21.5 mA) check calibration and linearisation Endress+Hauser...
  • Page 86: Application Errors In Liquids

    Interference echo from 1. Carry out tank mapping → measured value on installations, nozzle or basic setup filling/emptying 100% extension on the 2. If necessary, clean antenna antenna 3. If necessary, select better mounting position actual expected t → L00-FMR2xxxx-19-00-00-en-014 Endress+Hauser...
  • Page 87 Possible causes: 100% • Rough surface due to 2. Optimise alignment filling/ emptying (see Page 90) eingetreten • Agitator running 3. If necessary, select a better • Foam installation position and/or larger antenna E 641 erwartet t → L00-FMR2xxxx-19-00-00-en-018 Endress+Hauser...
  • Page 88: Application Errors In Solids

    2. If necessary, use top target positioner to aim antenna better to product surface (avoidance of actual interference echo) (see Page 90) 3. If necessary, clean antenna expected 4. If necessary, select better mounting position t → L00-FMR250xx-19-00-00-en-014 Endress+Hauser...
  • Page 89 Possible causes: 100% • fluidisation of the 2. Optimise alignment surface (see Page 90) actual • extreme dust 3. If necessary, select a better formation installation position and/or larger • angle of repose antenna E 641 expected t → L00-FMR250xx-19-00-00-en-018 Endress+Hauser...
  • Page 90: Orientation Of The Micropilot

    Turn the flange by one hole or screw the threaded boss by one eighth of a turn. Note the echo quality. Continue to turn until 360° is reached. Optimum alignment: L00-FMRxxxxx-19-00-00-en-002 Fig. 4: Vessel partly full, no interference echo obtained L00-FMRxxxxx-19-00-00-en-003 Fig. 5: Vessel partly full, interference echo obtained: Endress+Hauser...
  • Page 91 Micropilot M FMR244 with PROFIBUS PA Trouble-shooting L00-FMRxxxxx-19-00-00-en-004 Fig. 6: Vessel empty, no interference echo L00-FMRxxxxx-19-00-00-en-005 Fig. 7: Vessel empty, interference echo obtained Fix the flange or threaded boss in this position. If necessary, replace the seal. Carry out tank mapping, see Page 68. Endress+Hauser...
  • Page 92: Spare Parts

    6 .. .3 x . 2 4 .. .2 > 7 0 ° C t > 8 5 ° C i n a L00-FMR244xx-00-00-06-xx-001 Endress+Hauser...
  • Page 93 Terminal module 4pole, PROFIBUS PA, FOUNDATION Fieldbus 52014817 Terminal module 4pole, HART, ferrit (F12), GL marine certificate 52014818 Terminal module 4pole, PROFIBUS PA, FOUNDATION Fieldbus ferrit (F12), GL marine certificate 40 Display 52026443 Display VU331, version 2 50 Antenna assembly with process connection on request! Endress+Hauser...
  • Page 94 Micropilot M FMR244 with PROFIBUS PA 65 Sealing kit 535720-9010 consists of: 2 x gasket Pg13.5 FA 2 x O-ring 17.0x2.0 EPDM 1 x O-ring 49.21x3.53 EPDM 2 x O-ring 17.12x2.62 FKM 1 x O-ring 113.9x3.63 EPDM 1 x O-ring 72.0x3.0 EPDM Endress+Hauser...
  • Page 95 6 .. .3 x . 2 4 .. .2 > 7 0 ° C t > 8 5 ° C L00-FMR244xx-00-00-06-xx-002 10 Housing - for E+H service only! 11 Hood for terminal compartment 52005643 Hood T12 Endress+Hauser...
  • Page 96 50 Antenna assembly with process connection on request! 65 Sealing kit 535720-9010 consists of: 2 x gasket Pg13.5 FA 2 x O-ring 17.0x2.0 EPDM 1 x O-ring 49.21x3.53 EPDM 2 x O-ring 17.12x2.62 FKM 1 x O-ring 113.9x3.63 EPDM 1 x O-ring 72.0x3.0 EPDM Endress+Hauser...
  • Page 97: Return

    Micropilot M FMR244 with PROFIBUS PA Trouble-shooting Return The following procedures must be carried out before a transmitter is sent to Endress+Hauser e.g. for repair or calibration: • Remove all residue which may be present. Pay special attention to the gasket grooves and crevices where fluid may be present.
  • Page 98: Contact Addresses Of Endress+Hauser

    Trouble-shooting Micropilot M FMR244 with PROFIBUS PA 9.10 Contact addresses of Endress+Hauser Contact addresses can be found on our homepage "www.endress.com/worldwide". If you have any questions, please do not hesitate to contact your Endress+Hauser representative. Endress+Hauser...
  • Page 99: Technical Data

    • temperature = +20 °C (68 °F) ±5 °C (9 °F) conditions • pressure = 1013 mbar abs. (14.7 psia) ±20 mbar (0.3 psi) • relative humidity (air) = 65 % ±20% • ideal reflector • no major interference reflections inside the signal beam Endress+Hauser...
  • Page 100 — — 8.6 % — — — — — 22 % — 687.2 — — — — 41.8 % Note! When the pressure is known and constant, this measured error can, for example, be compensated by means of linearization. Endress+Hauser...
  • Page 101 (-40 °F ... +176 °F) ↑ Ordering information see Page 6 ε r ≥ 1,4 Dielectric constant • in a stilling well: ε r ≥ 1,9 • in free space: 10.1.6 Mechanical construction Weight • F12/T12 housing: approx 2.5 kg Endress+Hauser...
  • Page 102 Micropilot M FMR244 with PROFIBUS PA 10.1.7 Certificates and approvals CE approval The measuring system meets the legal requirements of the EC-guidelines. Endress+Hauser confirms the instrument passing the required tests by attaching the CE-mark. RF approvals R&TTE, FCC Overspill protection german WHG, see ZE 244F/00/de.
  • Page 103 Note! This supplementary documentation can be found on our product pages on www.endress.com. Supplementary • Technical Information (TI345F/00/en) Documentation • Operating Instructions "Description of instrument functions" (BA291F/00/en) • Safety Manual "Functional Safety Manual" (SD150F/00/en). • Certificate "German WHG" (ZE244F/00/de). Endress+Hauser...
  • Page 104: Appendix

    Note! The default values of the parameters are typed in boldface. L00-FMR250xx-19-00-01-en-037 Endress+Hauser...
  • Page 105 . point , comma measured dist. measured level detection window application par. not modified modified reset distance unit download mode L00-FMR250xx-19-00-02-en-037 Endress+Hauser...
  • Page 106: Description Of Functions

    Micropilot M FMR244 with PROFIBUS PA 11.2 Description of functions Note! A detailed description of the function groups, functions and parameters is given in the documentation BA291F/00/en "Description of the instrument functions of the Micropilot M" on the enclosed CD-ROM. Endress+Hauser...
  • Page 107: Function And System Design

    Refer to the above figure for the reference point for "E". The Micropilot is equipped with functions to suppress interference echoes. The user can activate these functions. They ensure that interference echoes (i.e. from edges and weld seams) are not interpreted as level echo. Endress+Hauser...
  • Page 108 The complete measuring system consists of: personal computer e.g. with Commuwin II or ToF Tool and Profiboard resp. Proficard segment coupler PROFIBUS DP ENDRESS + HAUSER PROFIBUS PA operating and display module VU 331 ENDRESS + HAUSER – FXA 193 ToF Tool L00-FMR2xxxx-14-00-06-en-002 Endress+Hauser...
  • Page 109 • with display and operating module VU 331, • with a Personal Computer, FXA 193 and the operating software ToF Tool. The ToF Tool is a graphical operating software for instruments from Endress+Hauser that operate based on the time-of-flight principle (radar, ultrasonic, guided micro-impulse). It assists with commissioning, securing data, signal analysis and documentation of the measuring point.
  • Page 110: Index

    T12 housing ....... . 27–28 tank installations....... . 13 Endress+Hauser...
  • Page 111 ........26 Endress+Hauser...
  • Page 112 Micropilot M FMR244 with PROFIBUS PA Index Endress+Hauser...
  • Page 113 Erklärung zur Kontamination und Reinigung Please reference the Return Authorization Number (RA#), obtained from Endress+Hauser, on all paperwork and mark the RA# clearly on the outside of the box. If this procedure is not followed, it may result in the refusal of the package at our facility.
  • Page 114 www.endress.com/worldwide BA249F/00/en/05.08 71073069 CCS/FM+SGML 6.0 ProMoDo 71073069...