Technical Information
Levelflex M FMP41C, FMP45
Guided Level-Radar
Smart Transmitter for continuous level measurement
in liquids.
Application
The Levelflex M is used for continuous level
measurement of liquids.
FMP41C for corrosive liquids and hygienic
requirements
• Highest chemical resistance
• Rod probes up to 13 ft (4 m), cable probes up to 100 ft
(30 m) measuring range
• With rod probe for food processing and
pharmaceuticals
• All wetted components: PTFE, FDA-listed, gap-free
FMP 45 for high pressure and/or temperature
• Temperature range:
-328 to +752°F (-200 to +400°C)
• Pressure range: -14 to 5800 psi (-1 to 400 bar)
• With second safety compartment:
gas-tight glass feed though
• Rod and coax probes up to 13 ft (4 m), cable probes up
to 115 ft (35 m) measuring range
The following interfaces are available for system
integration:
®
• HART
(standard) with 4 to 20 mA analog,
®
• Profibus
PA,
• F
™ Fieldbus
OUNDATION
TI386F/24/ae
Your benefits
• Measurement independent of product properties
as:
– density,
– dielectric constant,
conductivity.
• Measurement possible despite turbulent
surfaces or foam
• Easy menu-guided local operation via four-line plain
text display.
• Convenient remote operation, diagnosis and
documentation of the measuring point via the
ToF Tool operating program supplied free of charge
• Optional remote display and operation.
• Envelope curve presentation on the local display for
easy diagnosis.
• Electronics can be replaced without opening the tank
• Application in safety related systems (overspill
protection) with requirements for functional safety up
to SIL 2 in accordance to IEC 61508/IEC 61511-1
• Approvals:
– Europe: ATEX, EHEDG (FMP41C), PED (FMP45),
WHG.
– North America: FM, CSA, boiler act (FMP45).

Advertisement

Table of Contents
loading

Summary of Contents for Endress+Hauser Levelflex M FMP41C

  • Page 1 Technical Information Levelflex M FMP41C, FMP45 Guided Level-Radar Smart Transmitter for continuous level measurement in liquids. Application Your benefits The Levelflex M is used for continuous level • Measurement independent of product properties measurement of liquids. FMP41C for corrosive liquids and hygienic –...
  • Page 2: Table Of Contents

    Maximum measured error ......17 Levelflex M FMP41C ....... . . 39 Resolution .
  • Page 3: Function And System Design

    Levelflex M FMP41C, FMP45 Function and system design Measuring principle The Levelflex is a "downward-looking" measuring system that functions according to the ToF method (ToF = Time of Flight). The distance from the reference point (process connection of the measuring device (→ Page 30-31) to the product surface is measured.
  • Page 4: Equipment Architecture

    Levelflex M FMP41C, FMP45 Output The Levelflex is initially adjusted at the factory to the probe length ordered, so that in most cases, only the application parameters that automatically adapt the device to the measuring conditions need to be entered. For models with current output, the factory adjustment for zero point E and span F is 4 mA and 20 mA;...
  • Page 5 Levelflex M FMP41C, FMP45 FMP45 For high pressure and/or temperature. Version: FMP45- *K... FMP45- *A... FMP45- *L... FMP45- *M... FMP45- *C... FMP45- *N... Probe type: Rod probe Cable probe Coax probe Wetted materials: Stainless steel Stainless steel 316L/ Stainless steel 316L/1.4435,...
  • Page 6 Levelflex M FMP41C, FMP45 System integration via PROFIBUS PA Maximum 32 transmitters (depending on the segment coupler, 10 in the Ex ia IIC hazardous area according to the FISCO Model) can be connected to the bus. The Bus voltage is supplied by the segment coupler. Both local and remote operation are possible.
  • Page 7 Levelflex M FMP41C, FMP45 Integrated in tank gauging system The Endress+Hauser Tank Side Monitor NRF590 provides integrated communications for sites with multiple tanks, each with one or more sensors on the tank, such as radar, spot or average temperature, capacitive probe for water detection and/or pressure sensors.
  • Page 8 The number of instruments which can be connected in mutidrop mode can be calculated by the "FieldNetCalc" program. A description of this program can be found in Technical Information TI 400F (Multidrop Conncector FXN520). The program is available form your Endress+Hauser sales organization or in the internet at: "www.endress.com Download" (Text Search = "Fieldnetcalc").
  • Page 9: Input

    Levelflex M FMP41C, FMP45 Input The measured variable is the distance between the reference point (see Fig on → Page 30) and the product Measured variable surface. Subject to the input zero point empty distance (E, see Fig. on → Page 3) the level is calculated.
  • Page 10: Blocking Distance

    Levelflex M FMP41C, FMP45 Blocking distance The upper blocking distance (= UB) is the minimum distance from the reference point of the measurement (mounting flange) to the maximum level. At the lowest part of the probe an exact measurement is not possible, see "Performance characteristics" on →...
  • Page 11: Output

    Levelflex M FMP41C, FMP45 Output Output signal • 4 to 20 mA with HART protocol • Profibus-PA • FOUNDATION Fieldbus (FF) Signal on alarm Error information can be accessed via the following interfaces: • Local display: – Error symbol – Plain text display •...
  • Page 12: Auxiliary Energy

    Levelflex M FMP41C, FMP45 Auxiliary energy Electrical connection Terminal compartment Three housings are available: • Aluminum housing F12 with additionally sealed terminal compartment for: – standard, – Intrinsically safe (EEx ia). • Aluminum housing T12 with separate terminal compartment for: –...
  • Page 13: Terminal Assignment

    Levelflex M FMP41C, FMP45 Terminal assignment 2-wire, 4 to 20 mA with HART 4-wire, 4 to 20 mA active with HART AC / DC Power Display unit, Power recorder, PCS Alternatively Commubox Alternatively FXA191/195 Communication DXR375 resistor Commubox Communication (> 250 ) W...
  • Page 14: Fieldbus Plug Connectors

    Levelflex M FMP41C, FMP45 FOUNDATION Fieldbus The digital communication signal is transmitted to the bus via a 2-wire connection. The bus also provides the auxiliary energy. For further information on the network structure and earthing and for further bus system components such as bus cables, see the relevant documentation, e.g.
  • Page 15: Load Hart

    Levelflex M FMP41C, FMP45 Minimum load for HART communication: 250 Ω Load HART Supply voltage HART, 2-wire The following values are the voltages across the terminals directly at the instrument: Terminal voltage Current Communication consumption minimum maximum HART 4 mA...
  • Page 16: Current Consumption

    Levelflex M FMP41C, FMP45 Current consumption Current consumption Communication Output current Power consumption HART, 2-wire 3.6 to 22 mA — & 3 to 6 mA / & 3.5 VA HART, 4-wire (90 to 250 V 2.4 to 22 mA & 100 mA / & 1 W HART, 4-wire (10.5 to 32 V...
  • Page 17: Performance Characteristics

    Levelflex M FMP41C, FMP45 Performance characteristics Reference operating • Temperature = +68°F (20°C) ± 9°F (5°C) conditions • Pressure = 14.7 pisa (1013 mbar abs.) ± 0.3 psi (20 mbar) • Relative humidity (air) = 65% ± 20% • Reflection factor 0.8 (surface of water for coax probe, metal plate for rod and cable probe with min. 3 ft / 1 m ∅)
  • Page 18: Resolution

    8.6 % — — — — — 22 % — 687.2 — — — — 58 % Special versions of FMP45 are available which provide a compensation method for the gas phase influence. Please contact your local Endress+Hauser representative. Endress+Hauser...
  • Page 19: Operating Conditions: Installation

    Levelflex M FMP41C, FMP45 Operating conditions: Installation Probe selection (see overview on → Page 4) General instructions • In normal cases, use rod probes. Cable probes are used for measuring ranges > 13 ft (4 m) or when the overhead clearance does not allow the installation of rigid probes.
  • Page 20 Levelflex M FMP41C, FMP45 Type of probe mounting FMP41C • When installing in plastic tanks, the nozzle must have at least 2" (DN50). The appropriate flange must be used as the process connection. • For nozzles up to 18" (450 mm) high, select the length of the centering rod appropriate for the nozzle height when using rope probes.
  • Page 21 Levelflex M FMP41C, FMP45 Supporting probes against warping Rod probes: FMP41C and FMP45 Ø < 0.98” (25 mm) e.g. 0.12” (3 mm) FMP41C Probe rod c oated (FMP 41 C) Plastic sleeve e.g. PTFE, PEEK or PPS > 1.97” Short metal pipe (50 mm) e.g.
  • Page 22: Installing Fmp45 With Heat Insulation

    Levelflex M FMP41C, FMP45 Installing FMP45 • If process temperatures are high (≥ 392°F / 200°C), FMP45 must be included in normal tank insulation to with heat insulation prevent the electronics heating up as a result of heat radiation or convection.
  • Page 23: Special Instructions

    For FMP45: In vacuum applications and in applications where extreme condensate formation may occur, there is the danger that the vessel may be completely flooded. For media groups with high DC values, this may result in a measuring value lower than the actual level. Please contact your local Endress+Hauser representative for reme- dial actions.
  • Page 24: Installation For Difficult To Access Process Connections

    Levelflex M FMP41C, FMP45 Installation for difficult to Installation with remote housing access process connections • Follow installation instructions on → Page 19. • Mount the housing on the wall or pipe (in vertical or horizontal position as required) as shown in the diagram.
  • Page 25: Operating Conditions: Environment

    Levelflex M FMP41C, FMP45 Operating conditions: Environment Ambient temperature range Ambient temperature for the electronic: -40 to +176°F (-40 to +80°C) The functionality of the LCD display may be limited for temperatures T <-4°F (-20°C) and T >+140°F (60°C). A weather protection cover should be used for outdoor operation if the instrument is exposed to direct sunlight.
  • Page 26: Storage Temperature

    Levelflex M FMP41C, FMP45 FMP45 (XT 536°F / 280°C) If the temperature (T ) at the process connection is below > -40°F (-40°C) or above > +176°F (80°C), the permitted ambient temperature (T ) is limited as shown in the following diagram (temperature derating): Permitted ambient temperature T °F (°C)
  • Page 27: Operating Conditions: Process

    Levelflex M FMP41C, FMP45 Operating conditions: Process Process temperature range The maximum permitted temperature at the process connection (see figure measuring point) is determined by the process connection ordered: FMP41C Min. temperature Max. temperature Measured -40°F (-40°C) 392°F (+200°C) here For FMP41C with E+H universal adapter: 32°F to 302°F (0°C to 150°C).
  • Page 28: Dielectric Constant

    Levelflex M FMP41C, FMP45 FMP41C Material Approval Rod probe, Cable probe PFA (Daikin PFA AP230) FDA, 3-A Cladding PTFE (Dyneon TFM1600) FDA, 3-A FMP45 Rod and coax probe Cable probe Process connection Stainless steel 1.4435/316L Stainless steel 1.4435/316L Alloy C22...
  • Page 29: Mechanical Construction

    Levelflex M FMP41C, FMP45 Mechanical construction Design, dimensions Housing dimensions Dimensions for process connection and type of antenne → Page 30. 2.26” max. 4.33” 3.07” (110) (65) (78) ENDRESS+HAUSER Ø 5.08” (129) 5.91” (150) F12 housing (Aluminum) 3.35” (85) L00-F12xxxx-06-00-00-en-001 max.
  • Page 30 Levelflex M FMP41C, FMP45 Levelflex M FMP41C - process connection, type of probe Housing dimensions → Page 29. F12 / T12 / F23 housing Variant “3”: remote electronic 3.46” 4.84” (88) (123) 4 x Ø 0.33” 3.46” (8.5) (88) 108”...
  • Page 31 Levelflex M FMP41C, FMP45 Levelflex M FMP45 - process connection, type of probe Housing dimensions → Page 29. F12 / T12 / F23 housing Variant “3”: remote electronic 3.64” 4.84” (88) (123) 3.64” 4 x Ø 0.33” (88) (8.5) 108”...
  • Page 32: Tolerance Of Probe Length

    Levelflex M FMP41C, FMP45 Tolerance of probe length Rod probes over 3.2 ft (1 m) 9.8 ft (3 m) 20 ft (6 m) up to 3.2 ft (1 m) 9.8 ft (3 m) 20 ft (6 m) admissible tolerance in inches (mm) - 0.2 (- 5)
  • Page 33: Human Interface

    Levelflex M FMP41C, FMP45 Human interface Operation concept The display of the process value and the configuration of the Micropilot occur locally by means of a large 4-line alphanumeric display with plain text information. The guided menu system with integrated help texts ensures a quick and safe commissioning.
  • Page 34: Operating Elements

    Levelflex M FMP41C, FMP45 Operating elements The operating elements are located inside the housing and are accessible for operation by opening the lid of the housing. Function of the keys Key(s) Meaning Navigate upwards in the selection list Edit numeric value within a function...
  • Page 35: Local Operation

    Levelflex M FMP41C, FMP45 Local operation Operation with VU331 The LC-Display VU331 allows configuration via 3 keys directly at the instrument. All device functions can be set through a menu system. The menu consists of function groups and functions. Within a function, application parameters can be read or adjusted.
  • Page 36: Remote Operation

    Operation with ToF Tool The ToF Tool is a graphical operation software for instruments from Endress+Hauser that operate based on the time-of-flight principle. It is used to support commissioning, securing of data, signal analysis and documentation of the instruments. It is compatible with the following operating systems: WinNT4.0, Win2000 and WINXP.
  • Page 37 Levelflex M FMP41C, FMP45 Operation with FieldCare FieldCare is the Endress+Hauser FDT based Plant Asset Management Tool. It can configure all intelligent field devices in your plant and supports you in managing them. By using status information, it also provides a simple but effective means of checking their health.
  • Page 38: Certificates And Approvals

    Levelflex M FMP41C, FMP45 Certificates and approvals CE approval The measuring system meets the legal requirements of the EC-guidelines. Endress+Hauser confirms the instrument passing the required tests by attaching the CE-mark. See "Ordering information" on → Page 40-44. Ex approval German WHG.
  • Page 39: Ordering Information

    Levelflex M FMP41C, FMP45 Ordering information Levelflex M FMP41C Instrument selection Hazardous area EEx em Hazardous area Nonhazardous Certificate Intrinsically Safe (encapsulated) Explosion Proof area 1-½"/2"/3" DN 50 Flange 1-1/2” to 6” Universal- Tri-clamp dairy coupling (DN to 200) Process...
  • Page 40 Levelflex M FMP41C, FMP45 Ordering structure Levelflex M FMP41C Approval: A Non-hazardous area Non-hazardous area, WHG ATEX II 1/2G EEx ia IIC T6 Note safety instruction (XA) (electristatic charging)! ATEX II 2G EEx em (ia) IIC T6 Note safety instruction (XA) (electristatic charging)!
  • Page 41 Levelflex M FMP41C, FMP45 Ordering structure Levelflex M FMP41C (continued) Process Connection: DIN11851 DN50 PN40, PTFE >316L Clamp ISO2852 1-1/2", PTFE >316L Clamp ISO2852 2", PTFE >316L Clamp ISO2852 3", PTFE >316L Clamp ISO2852 1-1/2", PTFE >316L DRD 65mm PN40, PTFE >316L Clamp ISO2852 2", PTFE >316L, 3-A EHEDG...
  • Page 42: Levelflex M Fmp45

    Levelflex M FMP41C, FMP45 Levelflex M FMP45 Instrument selection Hazardous area Nonhazardous EEx em Hazardous area Intrinsically Safe area (encapsulated) Explosion Proof Certificate HT 752°F (400°C) XT 536°F (280°C) 1- ½" Flange Flange 1- ½" Process connection Type of probe...
  • Page 43 Levelflex M FMP41C, FMP45 Ordering information Levelflex M FMP45 Approval: A Non-hazardous area Non-hazardous area, WHG ATEX II 1/2G EEx ia IIC T6/IECEx Zone 0/1 ATEX II 1/2D, Alu blind cover ATEX II 1/2G EEx em [ia] IIC T6/IECEx Zone 0/1...
  • Page 44 Levelflex M FMP41C, FMP45 Ordering information Levelflex M FMP45 (continued) Prozessanschluss: Thread ISO228 G1-1/2, 200bar, 316L Thread ISO228 G1-1/2, 400bar, 316L Thread ANSI NPT1-1/2, 200bar, 316L Thread ANSI NPT1-1/2, 400bar, 316L, High pressure test Special version Power Supply; Output: 2-wire; 4 to 20mA HART D 2-wire;...
  • Page 45: Accessories

    Levelflex M FMP41C, FMP45 Accessories Weather protection cover A Weather protection cover made of stainless steel is recommended for outdoor mounting (order code: 543199-0001). The shipment includes the protective cover and tension clamp. F12 / F23 / T12 housing M IC...
  • Page 46: Remote Display Fhx40

    Levelflex M FMP41C, FMP45 Remote display FHX40 Pipe-mounting Wall-mounting (mounting bracket and plate (without mounting bracket) supplied optionally, see product structure) F12/F23 housing NEMA 6P (IP 68) 0.33” (8.5) Remote housing 5.9” (150) FHX 40 NEMA 4 (IP 65) O rd...
  • Page 47: Special Process Connection (Only Fmp45)

    Levelflex M FMP41C, FMP45 Special process connection Fisher flange 249B/259B (MVTF N0123) (only FMP45) 0.24” 1.14” (32) L00-FMP45xxx-00-00-06-de-001 Fisher flange 249C (MVTF N0124) 0.20” 1.14” (29) L00-FMP45xxx-00-00-06-de-002 Masoneillan flange (MVTF N0125) 1.14” 0.24” (29) L00-FMP45xxx-00-00-06-de-003 Endress+Hauser...
  • Page 48: Mounting-Kit Isolated (Only Fmp41C)

    Levelflex M FMP41C, FMP45 Mounting-kit isolated (only Mounting-kit Order - No. FMP41C) Reliable, isolated mounting for 0.16" (4 mm) cable probe 52014249 for 0.24" (6 mm) cable probe 52014250 If a cable probe has to be attached and a secure grounded...
  • Page 49: Commubox Fxa291

    Common Data Interface) to the USB interface of a personal computer or a notebook. For details refer to TI405C/07/en. Note! For the following Endress+Hauser instruments you need the "ToF Adapter FXA291" as an additional accessory: • Cerabar S PMC71, PMP7x • Deltabar S PMD7x, FMD7x •...
  • Page 50: Documentation

    Levelflex M FMP41C, FMP45 Documentation This supplementary documentation can be found on our product pages on "www.endress.com". Special Documentation Time of Flight Liquid Level Measurement Selection and engineering for the process industry, SD157F/00/en. Radar Tank Gauging brochure For inventory control and custody transfer applications in tank farms and terminals, SD001V/00/en.
  • Page 51: Certificates

    Levelflex M FMP41C, FMP45 Certificates Correlation of safety instructions (XA) and certificates (ZE) to the instrument: Safety instructions for WHG and ATEX (ZE and XA documents) can be viewed and downloaded from www.endress.com Correlation of Control Drawings (ZD) to the instrument:...
  • Page 52: Patents

    Levelflex M FMP41C, FMP45 Instrument Certificate Explosion Output Communication Housing protection FMP45 FM IS HART, 4...20 mA ZD075F/00/en PROFIBUS PA ZD106F/00/en FOUNDATION Fieldbus ZD109F/00/en HART, 4...20 mA B, D ZD076F/00/en PROFIBUS PA B, D ZD107F/00/en FOUNDATION Fieldbus B, D ZD110F/00/en...