Service menu
@
BOSCH
Menu item
Adjustment range
description
Screed
dry. H.
circ.
1
...
Yes
Screed drying in the selected heating circuit is active/not active
Screed
dry.
H. circ.
4
No
Start
I
Yes
Start screed drying now
I
No
Screed drying not yet started or terminated
- - - -
Interrupt
!
Yes
Temporarily stop screed
drying.
If the maximum interruption duration has been
exceeded,
a fault display is
No
output.
-::-
- - - -
--
Continue
Yes
Continue screed drying after stop.
INo
Table
30
Setting in the Screed drying menu
(Fig.
13
shows the default setting of the screed drying program)
30
~~-~-+-+-+~-
20
<-=t----r----r--+--+-+---r-+__
o
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22
6720
815
238-1
8 .10
Fig.
13
Screed drying process with default settings
t
Time
6.4
DHW
settings
~
i~
IIHW
')('lTlfll~S
!
DHW
syst
em
i
On
DHW
>
DHW
reduced
>
DHW circulation
p
ump
i
on
II
start
fre
quency DHW
eirc.
i
3/h
6 720 811 136-503.20
Fig.
14
DHW settings menu
The settings for the DHW system can be adapted in this menu
_
For
example,
here you can set the DHW temperature ranges for the various
operating modes or whether there is circulation in the DHW system. The
day and time for thermal disinfection are also set
here.
DHW heat pump 1
(DHW heat pump 2)
Off
On
TCxFlow temperature of heating circuit x (identical to system flow
tem-
perature TO if only one heating circuit is installed)
[]
The DHW system is activated by default when
delivered.
If no DHW system is installed, but one is activated
,
the
user interface indicates a fault.
~
If no DHW system is installed in the system
,
deactivate DHW system I in the Commissioning or
DHWmenu.
11
WARNING:
Risk of scalding!
I
The DHW temperature can be set above 60°C and
,
during thermal
disinfection,
the DHW is heated to above
60
°C.
~
Inform all people concerned and make sure that a
mixing device is
installed.
DHW
e.g.
15
...
60·C
...
65 ·C ON temperature and OFF temperature for the DHW operating
mode;
the adjustment range depends on the
installed heat
source.
DHWreduced
e.g. 15
...
45
...
60 ·C ON temperature and OFF temperature for the DHW reduced operating
mode;
the adjustment range depends
on the installed heat
source.
DHW circulation pump
On
I
If the OHW circulation pump is to be controlled by the heat
source,
the DHW circulation pump must be activated
here as well. The default setting depends on the installed heat
source.
I-
O ff
The DHW circulation pump cannot be controlled by the heat
source.
Table
31
Settings in the DHW menu
24
HPC
1\00 -
6
720821772 (2017/07)