The D8128D is also suitable for fire supervisory
applications, such as indicating circuit supervision
(using the D192G Bell Circuit Supervision Module),
sprinkler supervision, and valve tamper protection.
Use the D125B for two-wire smoke
detectors.
The D129 is usually used for water-flow
switches.

Figure 15: D8128D OctoPOPIT Layout

1 - Molex connectors
2 - Address DIP switches
3 - Terminal strip
4 - Point DIP switches
38
1
2
3
4
1
2 3 4 5
6 7 8
P O I N T S
Off-Board Points
9.4.3

Installation

For the most effective installation, use the following
four-step process:
1. Set the OctoPOPIT switches. Refer to Section

9.4.4 Setting the OctoPOPIT Switches.

2. Physically mount the OctoPOPIT in the
enclosure. Refer to Section 9.4.5 Mounting
OctoPOPITs on page 39.
3. Wire the OctoPOPIT. Refer to Section 9.4.6
Wiring OctoPOPITs on page 39.
4. Wire the OctoPOPIT sensor loops. Refer to
Section 9.4.6 OctoPOPIT Sensor Loops on page
42.
9.4.4
Setting the OctoPOPIT Switches
The D8128D OctoPOPIT has two sets of DIP
switches (Figure 15). Use the DIP switches on the top
of the unit (with the terminal strip along the left edge)
to set the address for the OctoPOPIT. Use the DIP
switches at the bottom of the unit to enable or disable
individual points connected to the OctoPOPIT.
Address Switches
The switches on the D8128D OctoPOPIT set point
assignments and line termination. These switches are
easier to set before mounting the D8128D in the
enclosure.
Switches 1, 2, 3, and 4 assign the OctoPOPIT sensor
loops to point numbers on the control panel. Table 13
shows the OctoPOPIT switch settings for point
assignments.
Switch 5 sets line termination. Refer to Table 14.
Table 13:

D8128D OctoPOPIT Switch Settings

ZONEX 1
Points 9 to 40
1
9 to 16
ON
17 to 24
ON
25 to 32
ON
33 to 40
ON
* Line Termination Switch
The D7212GV3 uses Points 9 to 40 on
Zonex 1 only.
Bosch Security Systems, Inc. | 10/10 | F01U143079-03
D8128D Address Switches
2
3
4
ON
ON
ON
ON
ON
OFF
ON
OFF
ON
ON
OFF
OFF