Heating/Cooling Settings; System Data - Bosch HPC 400 Installation Instructions For Contractors

User interface ems 2
Table of Contents

Advertisement

BOSCH
6.3
Heating/cooling
settings
I
System
data
Priority heating
eireu~
1
1---
Heating
eire.
1
Heating
eire.
2
Heating
eire.
3
>
I
Service menu
6.3.1
System
data
Settings for the entire system can be made in this menu. For
example.
the value for the minimum outside temperature or the thermal storage
capacity of the building can be set here. Additional settings for heating!
cooling circuit 1 are available
in
this menu (if directly connected to the
heat source).
6720 811 136-502.20
Fig.
6
Set heating/cooling menu
Config.
HCl at appliance
D
I
Min.
outdoor
temperature
Damping
Type of building
No
own
heating
circuit
pump
Via pump PC1
-35
...
-10
...
10 °C
No
Heavy
I
Medium
Light
No
Yes
Yes
r
rost sensor
coolin-
g
- -
- - - - -
-
-
--
~
Table 24 Settings in the system data menu
1) Valid
only for exhaust air heat
pumps.
Minimum outside temperature
Hydraulic and electrical connection of heating/cooling
circuit 1
to
device.
I
The
internal
pump of the heat
source is
also used as the pump
in
heating/cooling
circuit 1.
A buffer cylinder
I
is
not
required.
Heating/cooling
circuit
1
is
not directly connected to the heat
source.
In
this
case.
a buffer
cylinder is
not
installed (see
previous menu
item).
Pump PCl in heating/cooling
circuit 1 is
electrically connected
to
the
heat
source.
There is
a bypass between heating/cooling circuit 1 and the heat pump for the purposes
of
hydraulic separation.
1
-
With weather-compensated control the minimum outside temperature affects the heating
curve
(7 Minimum outside
temperature.
page 17 and Menu
for
setting of the heating
curve.
page
20)
.
The set
building type affects the measurement of the outside
temperature.
The
outside temperature
is
delayed
(dampened).
The
measured outside
temperature is
included unadjusted
in
the weather-compensated
control.
Measure of the thermal
storage capacity
of the heated building
(7 Type
of
building.
page
17).
High storage
capacity.
significant damping of the
outside temperature.
e.g.
brick building
Medium storage
capacity.
~edium
damping of the outside temperature. e.g. hollow
concrete
blocks
Low
storage
capacity.
low
damping of the
outside
temperature.
e.g.
prefabricated building.
wood-frame-'
construction
Frost sensor for cooling
installed.
No
frost
sensor for cooling
installed.
The minimum outside temperature
is
the average value of each of the
coldest outside temperatures or recent years. and
it
has an influence on
the heating
curve.
The value for the region can be taken from the
required heat load calculation that should be done for every building or
from the climate zone chart or from
Tab.
25.
~
Set the minimum outside design temperature for the heating
system.
London
-
1
Rome
- 1
Budapest
Madrid
- 4
Sevastopol
-12
Bucharest
Marseilles
- 6
Stockholm
-19
Hamburg
-12
Moscow
-
30
Valencia
- 1
I
Helsinki
-
24
Naples
- 2
Vienna
-15
Istanbul
- 4
Nice
±
0
Zurich
-16
Table 25 Minimum outside temperatures for Europe
Type of building
If damping is activated. the adjustment of the outside temperature
fluctuations can be set with the building type. By adjusting the outside
temperature thermal
inertia
of the building mass
is
taken into account.
Thus. by setting the building type the control can be adapted to suit the
characteristics of the building.
aOc
+-________ -.
__________
~
ah
12 h
24 h
6720 645
480-30.10
Fig.
7
Example for adjusted outside temperature:
[1]
current outside temperature
[2]
adjusted outside temperature
This greatly simplified example shows how the adjusted outside
temperature
follows
the current outside
temperature.
but does not
reach
its
extreme values.
HPC 400 - fi 720821 -72 (201
11
0/
1
17