Troubleshooting
Acceptable Size and Duration of Power Line Voltage Fluctuations
The Motor Control Module is designed to withstand volt-
age fluctuations from the incoming power supply. If the
incoming power supply goes outside of the tolerable
range, an over-voltage condition is flagged and the sys-
tem shuts down in an alarm state. Excessive or
repeated over-voltage may permanently damage hard-
ware. The chart below shows the permissible magnitude
and duration of temporary over-voltage events. Consult
a qualified electrician if there are any concerns about
the available power supply.
1400
1200
1000
800
600
400
200
0
0.000001
54
Maximum Permissible Transient Voltage Surges
* Constructed from ITIC 1996 curve, referenced by IEC 61000-2-4
<--1 MW Max Surge Power
1200Vac, 1697Vdc
480Vac, 679Vdc
336Vac, 475Vdc
0.00001
0.0001
<--150 KW Max Surge Power
<--50 KW Max Surge Power
288Vac, 407Vdc
0.001
0.01
0.1
Time (seconds)
<--No Power Limit
264Vac, 373Vdc
1
10
313873J