14.2.4.4 Connecting the Data Acquisition Module DDAU
The measurement circuits are connected using connection modules (plug-in module III) at the
rear of the DAU.
Maximum wire gauges to be used for analog channels:
2
1.5 mm
(AWG 15) stranded
2
2.5 mm
(AWG 13) single-wire
Cable, e. g., LIYEB-CY 4 x 2 x 0.75 mm
Crimp contacts: see 2 in Table 14-1.
Maximum wire gauges to be used for binary channels:
2
1.5 mm
(AWG 15) stranded
2
2.5 mm
(AWG 13) single-wire
Cable, e. g., LIYEB-CY 16 x 2 x 0.25 mm
Crimp contacts: see 2 in Table 14-1.
14.2.4.5 Connecting the Data Acquisition Module BDAU
The binary inputs are connected using connection modules (plug-in module III) at the rear of the
BDAU.
Maximum wire gauges to be used for binary channels:
2
1.5 mm
(AWG 15) stranded
2
2.5 mm
(AWG 13) single-wire
Cable, e. g., LIYEB-CY 16 x 2 x 0.25 mm
Crimp contacts: see 2 in Table 14-1.