1 Product information SIMEAS R

A.1
Product information SIMEAS R
Scope of supply
With this consignment you have received one of the following products:
Firmware SIMEAS-R
V21.66 for 486-CPU with 16 MB memory
V23.16 for 486-CPU with 32 MB memory
V30.16 for Elan-CPU
Note
To upgrade the SIMEAS R firmware, please refer to the installation instructions
(document number: E50417-X1074-C306-A3).
Restrictions
Please notice the following restrictions using SIMEAS R:
Compatible OSCOP P versions
This firmware is compatible with OSCOP P V6.40 or higher.
Actions needed after firmware update
a) After a firmware update, you have to use the parameterization software OSCOP P to
decrease all memory sizes for the analog fault recorder, the power and frequency recorder,
the mean value writer and for voltage dips by 1 MB.
This action is necessary for an update from V2.1.64 or lower to V21.66, from V2.3.14 or lower
to V23.16 and from V3.0.14 or lower to V30.16!
This action is not necessary for an update from V2.1.65 to V21.66, from V2.3.15 to V23.16
and from V3.0.15 to V30.16!
Note
Decreasing the memory sizes will reorganize the database. The device will then be reset: During
the reset, all data will be deleted in the memory and the memory segments will be created again.
This action will be displayed by blinking LEDs on the front panel.
Do not switch off the SIMEAS R during this activity!
Save all SIMEAS R data before changing the memory sizes.
b) The log system of the current firmware was extended. To allow OSCOP P < V6.60 to dis-
play all log messages in plain text, you have to replace text files in the OSCOP P installation
directory.
Proceed as follows:
Exit OSCOP P. Load the file OSCOP_P_V6.50_SIMEAS_R_Logs_Patch_1.zip from the
website http://www.powerquality.de --> Software --> OSCOP P.
Save the file in the OSCOP P installation directory. Uncompress the file. Confirm that the files
276