Commissioning; Start-Up Of The Simeas R-Pmu - Siemens SIMEAS R-PMU Manual

Digital fault recorder
Hide thumbs Also See for SIMEAS R-PMU:
Table of Contents

Advertisement

14.4

Commissioning

WARNING
Warning about dangerous voltages in electrical equipment during operation of the device.
Nonobservance of the safety instructions means that death, heavy injuries or consider-
able material damages can occur.
Only qualified personnel should work on and around this equipment. They must be
thoroughly familiar with all warnings and safety notices in this instruction manual as well as
with the applicable safety steps, safety regulations, and precautionary measures. Particular
attention must be drawn to the following:
Before making any connections, the device must be earthed.
Dangerous voltages can arise in all switching components connected with the power supply
and with the measuring and test voltages.
Hazardous voltages can be present in the device even after the power supply voltage has
been removed (capacitors can still be charged).
The limit values given in Technical Data must not be exceeded, this must also be taken into
account during inspection and commissioning.
14.4.1

Start-up of the SIMEAS R-PMU

Note
The SIMEAS R-PMU is delivered with standard parameterization! Information regarding the
standard parameterization can be found in the Appendix.
Booting
If the SIMEAS R-PMU is switched on or booted after the parameters have been set, the 16 LEDs
at the front side of the SIMEAS R-PMU indicate different operating conditions during booting.
When a parameterized device is switched on, all 16 LEDs of the front panel light up for approx.
two minutes. During this time, the operating system and the firmware are loaded. Depending on
the parameters set, all or most of these 16 LEDs are extinguished. The directory of the
incorporated flash memory is read and the DAUs are prepared for measurement. This process
lasts for approx. one and a half minute. Afterwards, the Device ready for operation LED lights
up and the device is ready for measurement.
The following deviations are possible during booting:
Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
14
14.4 Commissioning
207