12.11 Slot Description
Note
Digits following a point are regarded as decimal places.
Select under Display in OSCOP P whether the values of the channel are to be displayed in
the OSCOP P Evaluate module.
The display curve for low measured values can be improved by a gain factor that acts like a
zoom in the y direction. Enter the value in the Gain box.
Default setting: 1, i. e. no gain; digits following the point are regarded as decimal places.
Note
On the basis of the Nominal transducer values, OSCOP P calculates the standard trigger
values (nominal value ±20 %) and stores them for each channel of the analog fault recorders.
156
Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012