A waiting time of 1000 ms has been preset.
Note
If the data interface is used for the PMU, the baud rate is set to 115,200 bit/s (fixed). You can
only parameterize Direct and HAYES Modem. By activating the PMU, the baud rate will be set
to 115,200 bit/s automatically. Your previous baud rate parameterization will be lost.
Adjust the INIT String to suit your modem if necessary. It depends on the modem type that
is used. The default setting of the INIT string is: ATQ0V1E0X0S0=1.
Enter the supplementary command for an AT command in the Command Suffix box. The
default setting of the supplementary command is: ^M
Enter the command for the end of the command line in the Dialing Command box. The
default setting of the command is ATDT for tone dialing and ATDP for impulse dialing.
If a modem is used, check the message texts for the following conditions: Connect, Busy,
No dial tone and Disconnect and adjust them if necessary.
Note
Set the same baud rate for the SIMEAS R-PMU and the PC or DAKON.
Note
Always enter an INIT string for dial-up modems.
Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
12