Changing codes
Function
"Type room controller"
(see page 160)
"Room temp limitation"
"Quick setback" (setback
mode)
"Opt start max opt ener-
gy" (see page 153)
"Start optimisation max.
advance" (see
page 153)
"Optimum stop control
max. advance" (see
page 153)
"Start - room temp - re-
duced setpoint - in-
crease"
"End - room temp - re-
duced setpoint - in-
crease"
"Frost prot plant HC
pump"
"Mixer setpoint boost"
(differential temperature)
"Actuator running time"
(cont.)
Code
Operat-
ing level
1059
"F2"
1060
"F2"
1080
"F2"
1089
"F2"
1090
"F2"
1091
"F2"
1100
"F2"
1101
"F2"
1110
"F2"
1130
"F1"
1134
"F2"
Setting options
Delivered
condition
■ "Manually"
"Radiator
■ "Radiator
medium"
fast"
■ "Radiator me-
dium"
■ "Radiator
slow"
■ "Floor heat
fast"
■ "Floor heat
medium"
■ "Floor heat
slow"
- - -/0.5 to 4.0 °C
2.0
■ "Off"
"Down to re-
■ "Down to re-
duced set-
duced set-
point"
point"
■ "Down to frost
prot setpoint"
0 to 480 min
240
(00:00:00 -
00:80:00)
0 to 360 min
0
(00:00:00 -
00:06:00)
0 to 360 min
60
(00:00:00 -
00:06:00)
- - -/-30 to 10 °C
-5
-30 to 10 °C
-14
■ "Off"
"On"
■ "On"
0 to 50 °C
8
30 to 873 s
120
Codes
97