Commissioning, inspection, maintenance
Further details regarding the individual steps
1. Close shut-off valves A and B on
the heating water side (lever to the
right).
2. Connect the drain hose to valve D
and connect it to a drain outlet.
3. Open valves C and D and vent
(flush) using mains pressure until no
more air noise is audible.

Venting the heating system

1. Vent heating system by bleeding the
radiators.
Vent the heating water buffer cylinder
separately when operating with a
multi mode heating water buffer cyl-
inder (see page 8).
64
B
(cont.)
C
A
4. Close valves C and D, open shut-
off valves A and B on the heating
water side.
5. Adjust system pressure at fill valve
C to > 1.0 bar.
2. Check the system pressure.