Troubleshooting
Fault messages
Fault mes-
Cause
sage
"298: False
The Eng burner ionisation
flame Eng
electrode has detected a
bu"
faulty flame.
"299: False
The auxiliary burner ionisa-
flame supp
tion electrode has detected a
bu"
faulty flame.
"300: Eng
Stirling head control temper-
head undert
ature too low.
SW"
132
(cont.)
Remedy
Check the gas supply. Check
gas type setting (see
page 66).
Check electrodes (see
page 73).
Check function of gas train
and ignition transformer.
Check balanced flue system.
Ensure that flue gases are
not being recirculated.
If the fault has not been rec-
tified, replace the control unit
PCB (see page 138).
Check thermocouple cables.
If the fault has not been rec-
tified, replace the control unit
PCB (see page 138).